Review Status: Requires Resubmit

Review Details: PRE-APPLICATION CONFERENCE REVIEW v.1

Plan Number - TP-PRE-0123-00074
Review Name: PRE-APPLICATION CONFERENCE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Historic REQUIRES RESUBMIT Project requires more information on how the historic structures will be treated. How will the rear portions of the buildings be treated? Removal of the rear should not impact the overall integrity.
Demolition of two contributing structures and retention of only the facade is not consistent with the US Secretary of the Interior's Standards. Alternate designs that retain the buildings should be considered.
Design Review REVIEW COMPLETED Design Professional now available in PRO:

Rick Gonzalez, Architect
214 E Suffolk Drive, Tucson, Az. 85704
(520) 850-7401 gonzalezrick34@gmail.com
DATE: January 29, 2023
TO: Maria Gayosso, Urban Planner/Principal Planner/Project Manager,
City of Tucson
FROM: Rick Gonzalez, Architect (#26992)
COT On-Call Design Professional
RE: Design Professional Review Letter 1, Presubmittal TP-PRE-0123-00074,
Solot Block Redevelopment
I have reviewed the Urban Overlay District Design Preliminary Site Plan for the
Solot Block Redevelopment submitted January 2023 for the purpose of
determining its conformance with the Requirements of the Sunshine Mile District
(SMD) Mid-Century Sub-District. I have checked the submittal against the
Submittal Requirements in the The Sunshine Mile Overlay Document. I
recommend addressing the comments as indicated below:
Submittal Requirements Status
1. Placement and Setback Requirements Complies
2. Building Heights and Height Setbacks Show for 2 modified
Buildings if applicable
3. Floor Uses Label- if 2 above
applies
4. Lot Coverage, Open Space (non-res 30%) Indicate on Site Plan
5. Minimum Landscape Area (50% of Open Indicate on Site Plan
Space [O.S.])
6. Massing (1 story 50' max. unbroken) N/A - Existing
7. Proposed Building(s) – Respect scale Provide an Elevation if
modified above
existing facades
8. Scale defining architectural elements Provide if item 7
applies
9. Vehicular Parking Elaborate on approach
to Mobility and
Parking as outlined in
SMD Integrated
Planning Document
Section H.
10. Bicycle Parking Refer to Item 9 above
11. Pedestrian Access and Pathway Shade Refer to Item 9 above;
Shade – refer to
Section E (page III-10)
– Show on 50% of
pathways
12. Utilities: Show utilities on site plan Add to Site Plan
13. Off-Street Loading Part of Overlay Relief
Request?
14. Solid Waste Collection Provided, verify
Environmental
Services Approval
General Comments
1. Address Preliminary Comments 2,3,4,5,7,8,9,10,11,12, and 13 above for your
initial submittal.
Thank you, Rick Gonzalez, Architect
Fire New Construction REVIEW COMPLETED Section 503.2.5 Dead ends. Dead-end fire apparatus access roads in excess of 150 feet (45 720 mm) in length shall be provided with an approved area for turning around fire apparatus.
Changes of uses may require new codes being met
Please call or email to set up a meeting to discuss this project further with TFD

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
Site Engineering REVIEW COMPLETED Project: TP-PRE-0123-00074
Address: 2545 E Broadway Bl

1. Ensure waste maneuverability and design per TSM 8-01
a. Ensure Clearance height for waste solid waste disposal is 20ft.
2. Maximize Water Harvesting into any new landscaping areas
3. Show sidewalk connectivity onto frontage (TSM 7-01)
4. Show vehicle maneuverability in north east area of the parking lot
5. All required parking shall be accommodated onsite (Sunshine Mile District IV-36)
a. If a waiver is applied for, a shared parking agreement will be required

Scott Haseman
scott.haseman@tucsonaz.gov
Site Landscape REVIEW COMPLETED CDRC TRANSMITTAL

PROJECT: SOLOT BLOCK DEVELOPMENT
ACTIVITY NO. TP-PRE-0123-00074
ADDRESS/PARCEL: 2545 E BROADWAY BL/125-09-012A
ZONING: C-1; UOD-3 MID-CENTURY SUBDISTRICT

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. This plan has also been reviewed for compliance with the Sunshine Mile Overlay District and Mid-Century UOD.

The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Landscape/NPPO to assure compliance with the applicable UDC development criteria and Technical Standards.

COMMENTS:
1. A landscape plan is required per 7.6.2.B.1-b. The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development to submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4 and Administrative Manual 2-10.
2. Per the Sunshine Mile Overlay District and the Mid-Century Overlay, the minimum landscape requirements only apply to Public Open Spaces, see page IV-39.
3. Per Section J (page III-23) Open Space #7, “Parking areas may not be counted as Open Space.”
4. Ensure the required number of trees is in all vehicular parking areas (1 tree: 4 parking spaces) per UDC 7.6.4.B.1. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.
5. Under Section M Environmentally Conscious Design, which outlines that each project shall include ten (10) or more of the following design practices., #3 states that “Shade is required for 70% of parking areas”. While this is not a hard requirement, please keep that in mind as part of this development.
6. There will need to be a street landscape border on E Broadway Bl per UDC 7.6.4.C-2 and Table 7.6.4-1. See UDC 7.6.4.C for landscape border requirements.
7. In Section E of the Sunshine Mile Overlay District Shade (page III-10), “...shade shall be provided for at least fifty (50) percent of all sidewalks and pedestrian paths as measured at 2:00 pm on June 21 when the sun is 82 degrees above the horizon. Shade may be provided by trees, arcades, canopies, or shade structures provided their location and design characteristics are compatible with the historic and design context of the street and the architectural integrity of the building. The use of plantings and shade structures in the City Right-Of-Way is permitted to meet this standard with the approval of DTM.”
8. See Engineering notes for Retention/Detention.
9. All landscape plans shall incorporate water conserving design as defined in UDC Section 7.6.6, Use of Water, and as described in the Technical Standards Manual 5.01-5.11.
10. The Landscape Plan should match the Commercial Rainwater Harvesting Plan as well as the Grading Plan. Please include spot elevations in the detention/retention areas as well as in all water harvesting areas in the Landscape Plan.
11. Maximize the rainwater harvesting across the site into the landscape areas, including but not limited to the street landscape borders as well as the tree wells for the required trees for the parking lot. One way to accomplish this would be the use of flush curbs and parking blocks.
12. Commercial Rainwater Harvesting plan is required per UDC Technical Standards Manual – Section 4-01.3.0. and Section 5-01.0.0 Landscaping and Screening. Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. Using Low Impact Development design and water harvesting provides critical basin detention and first flush retention for all new development and impervious area. The newly adopted Detention/Retention Manual can be found: https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-final-201406-manual.pdf

With CoT edits to the manual are found at: https://www.tucsonaz.gov/files/pdsd/codes/Detention_Retention_Manual_Tech_Standards_Amemdments.pdf

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov or 520-837-4988
Site Zoning REVIEW COMPLETED CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Nicholas Martell, Principal Planner
PROJECT: Thursday Pre-submittal meeting - TP-PRE-0123-00074
Address: 2545 E BROADWAY BL
Parcel: 12509012A
Zoning: C-1
Existing Use: Vacant
Proposed Use: None Proposed
TRANSMITTAL DATE: February 1, 2022

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. All uses will be determined by UDC 4.8-4: Permitted Uses. The Sunshine Mile District Manual may allow for different uses.
3. Parking is calculated as follows (Table 7.4.4-1 UDC). The Sunshine Mile District Manual addresses parking in section H and may be used to relieve parking requirements.
4. The proposed improvements are within the UOD-3 Mid-Century Subdistrict. The subdistrict is broken up into two categories: The Midcentury Subdistrict, and the Restricted Uses District. This development is within the Midcentury Subdistrict and is subject to the uses starting on page III-4 of the document. Please contact me with any questions about applicable uses.
5. The project is in the Rio Nuevo Multipurpose Facilities District.
6. The maximum height of a structure in the zone, for a non-residential use, is 30’.
7. The proposed driveway appears to be cutting through one of the buildings on the west. A historic demolition would be required to demolish part of the building.
8. It is unclear whether the parking spaces to the North would be accessed from the alley. Vehicular maneuvering can only be done on-site.
9. Ensure bicycle parking is provided per article 7.4.8 of the UDC.
10. Perimeter yard setbacks can be found in TABLE 6.3-4.A: DIMENSIONAL STANDARDS. The Sunshine Mile District overlay may allow for modifications to the UDC.
11. Please provide a cross access agreement if access to and from the parcel will cross between parcels.
12. Ensure the vehicle use area is compliant with 7.4.6 of the UDC. A fully dimensioned plan is required upon submittal of the Development Package. Some of the vehicle parking spaces do not appear to meet circulation standards in 7.4.6.F.
13. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met.
14. Upon submission of the Development Package, please reference the codes from the Unified Development Code (UDC). The plans will be reviewed through the lens of the UDC; any Sunshine Mile reductions to standards will be addressed in subsequent submissions. Do not hesitate to set up a meeting with staff to discuss application steps.
15. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.
If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov
Traffic Engineering Review REVIEW COMPLETED No Comments
TW Hydraulic Modeling Review REVIEW COMPLETED 1. Tucson Water has no objections to the proposed development and offers the following comments for your convenience.
2. This group of buildings is currently served by an existing 6” dead end water main on the north side of the Broadway Boulevard right of way. No fire service line larger than 4” may be connected to this dead end water main.
3. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106