Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2024 Fire New Construction REQUIRES RESUBMIT TF-FCP-0923-01162 • Fire Construction Review v5 •1001 N PARK AV TUCSON, AZ 85719
Based on the information provided, I am requesting corrections for the following:

Sheet FP-2:
Update pump start/stop notes to match the actual (see mark up on plan for more info)
See NFPA 20 - 4.7.7 for requirements for pressure-regulating devices.
Hydrostatic tests to be 50psi above system (196 psi static) NFPA 13 - 25.2.1.2
Refer to NFPA 14 - 7.2.4 for the required arrangement of pressure-regulating devices

Sheet FP-3
Provide hose connection at roof in accordance with NFPA 14 - 7.3.2.9

Sheet FP-4
Clarify heads spaced too closely at column line 2.2 between H & L

Sheet FP-5
Provide hose connections in accordance with NFPA 14 - 7.3.2.1

Sheet FP-9
Provide coverage at closet in accordance with 2016 NFPA 13, 8.15.8.
Provide coverage at WC 1121A&B, Pool Equipment (if deck above) NFPA 13, 2016ed 8.1.1

General Comments:
Room names at common areas, NFPA 13 - 23.1.3
Provide air vent(s) in accordance with NFPA 13 - 7.1.5
Include max (calculated) spacing for sprinklers (EC and Res.)
Questions: patricia.shelton@tucsonaz.gov
02/01/2024 TFD Application Completeness Check REVIEW COMPLETED