Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.5
Permit Number - TF-FCP-0923-01162
Review Name: FIRE CONSTRUCTION REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/14/2024 | Fire New Construction | REQUIRES RESUBMIT | TF-FCP-0923-01162 • Fire Construction Review v5 •1001 N PARK AV TUCSON, AZ 85719 Based on the information provided, I am requesting corrections for the following: Sheet FP-2: Update pump start/stop notes to match the actual (see mark up on plan for more info) See NFPA 20 - 4.7.7 for requirements for pressure-regulating devices. Hydrostatic tests to be 50psi above system (196 psi static) NFPA 13 - 25.2.1.2 Refer to NFPA 14 - 7.2.4 for the required arrangement of pressure-regulating devices Sheet FP-3 Provide hose connection at roof in accordance with NFPA 14 - 7.3.2.9 Sheet FP-4 Clarify heads spaced too closely at column line 2.2 between H & L Sheet FP-5 Provide hose connections in accordance with NFPA 14 - 7.3.2.1 Sheet FP-9 Provide coverage at closet in accordance with 2016 NFPA 13, 8.15.8. Provide coverage at WC 1121A&B, Pool Equipment (if deck above) NFPA 13, 2016ed 8.1.1 General Comments: Room names at common areas, NFPA 13 - 23.1.3 Provide air vent(s) in accordance with NFPA 13 - 7.1.5 Include max (calculated) spacing for sprinklers (EC and Res.) Questions: patricia.shelton@tucsonaz.gov |
||
02/01/2024 | TFD Application Completeness Check | REVIEW COMPLETED |