Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0823-01040
Parcel: 11620637A

Address:
165 S LINDA AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0823-01040
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2023 Fire New Construction REQUIRES RESUBMIT For information on resubmittals see: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

Provide hydraulic signage in accordance with NFPA 14 –6.8.3
Provide hose connections in accordance with NFPA 14 - 7.3.2.1
Provide information in/for hydraulic calculations in accordance with NFPA 13 - 23.4.4.5
Provide coverage at trash chute in accordance with NFPA 13 –22.15.2.2.1.4
Provide air vents in accordance with NFPA 13 - 7.1.5
Provide room names, soffits, lights, diffusers, ceiling heights in accordance with NFPA 13 - 23.1.3
Provide make, model, rating of pump on plan in accordance with NFPA 20 - 4.2.3.1
Clarify check valves at riser, backflow, etc. Showing gate valve instead of butterfly on calcs, backflow on plans not on calcs, check valve on calc not on plan, etc.
Please review drawings for spacing issues.
Note sizes/locations of Steel/CPVC (general note on plan would imply CPVC at Garage)
Questions: patricia.shelton@tucsonaz.gov or 520.837.7082
08/29/2023 TFD Application Completeness Check REVIEW COMPLETED