Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0823-01040
Parcel: 11620637A

Address:
165 S LINDA AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0823-01040
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2023 Fire New Construction REQUIRES RESUBMIT Hose valves for stand pipe are still located at the intermediate levels. NFPA 14 and Tucson Fire require hose connections at the floor landings.
11/29/2023 TFD Application Completeness Check REVIEW COMPLETED