Permit Number: TF-FCP-0726-00467
Parcel: 11620637A

Address:
165 S LINDA AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW REVISION v.1

Permit Number - TF-FCP-0726-00467
Review Name: FIRE CONSTRUCTION REVIEW REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2026 Fire New Construction REQUIRES RESUBMIT Fire Alarm (FA) Reviewer
Steven Taulbee; staulbee@safebuilt.com
Discipline Status:Denied
Date Completed: 9/3/2026
General Comments:
1. Provide Design Professional information on the plans as required. 2022 NFPA 72, 7.4.4, State of Arizona Law.
Plans:
1. Indicate on Fire Alarm Plans revisions. Show areas that are revised and/or changed in a "clouded format". 2022 NFPA 72,
7.5.5
08/24/2026 TFD Application Completeness Check Express REVIEW COMPLETED