Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0123-00325
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2023 | Fire New Construction | REQUIRES RESUBMIT | Update drawings in accordance with NFPA 13, 2016ed 23.1, to include ceiling heights, room identification, partitions (i.e. mail room), etc. Provide floor control assemblies in accordance with NFPA 13, 2016ed. Provide isolation valves for standpipes in accordance with NFPA 14, 2016 – 6.3.2 Provide air vents in accordance with NFPA 13, 2016ed 7.1.5 Verify hose connections are provided at roof in accordance with NFPA 14, 2016 - 7.3.2.9 Verify coverage at "Stair D" For information on resubmittals see https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf Questions: patricia.shelton@tucsonaz.gov / 520.837.7082 |
||