Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1224-02437
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2025 | Commercial Electrical | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 1/29/2025 9:54:47 AM E101 POWER PLANS: could not locate Note 2 |
||
| 02/07/2025 | Outdoor Lighting | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 1/29/2025 9:54:47 AM E101 POWER PLANS: could not locate Note 2 |
||
| 01/23/2025 | Water - PDSD | APPROVED | |||
| 02/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/07/2025 | Commercial Building | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 2/6/2025 12:24:51 AM 1. SHEET S101 - SPECIAL INSPECTIONS: The Statement of Special Inspections included in the structural general notes, Sheet S101, appears to be incomplete. Please amend the statement to include the following required special inspections per the 2018 International Building Code: i. Open-Web Steel Joists per the 2018 IBC, Table 1705.2.3. ii. Post-installed and cast-in-place anchors per the 2018 IBC, Table 1705.3, Items 3 & 4 2. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 1/23/2025 2:53:32 PM |
||
| 02/07/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 2/3/2025 1:50:19 PM 1. General - Provide Heat Load calculations. Show all O/A Ventilation in the load calculations. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. |
||
| 02/07/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 2/6/2025 9:40:33 PM First Plumbing Review:' 1). General Plumbing Plans: Missing roof drain conductor illustrations & sizing calculations. Add roof drain conductor illustrations & sizing calculations. -2018 IPC 1106.1, 1106.2 2). Plan pages P1 & P3: Missing Gray water system detail. Add Gray Water System Detail to the Plumbing Plans. 2018 IPC 301.3 3). Plan Page P-3: Sanitary riser missing 1st floor & 2nd floor Service sink piping illustrations. Add 1st floor & 2nd floor Service sink piping illustrations.-2018 IPC 106.3.1, 901.2.1 4). Plan Page P-0: Fixture schedule missing Manufacturer names & model numbers for fixtures & water Heater. Add Manufacturer names & model numbers for fixtures & water Heater to the fixture schedule. -2018 IPC 303 5). Plan Page P-0: 30 Gallon Water Heater appears to be undersized for the demand shown. Provide information that shows the 30 Gall =on WH will supply enough hot water to all the fixtures. -2018 IPC 607.1 |
||
| 01/23/2025 | Site Engineering | REQUIRES RESUBMIT | 1. Phase 2 of the development package TD-DEV-0223-00144 must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
| 01/24/2025 | Site Zoning | REQUIRES RESUBMIT | See Engineering comments. Additional comments may be forthcoming. | ||
| 01/15/2025 | Fire New Construction | REVIEW COMPLETED | Fire Alarm and Fire Sprinklers Systems requires a separate submittal and permit. | ||
| 12/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |