Permit Number: TC-COM-1224-02437
Parcel: 13809002E

Address:
5951 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1224-02437
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2025 Commercial Electrical APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/29/2025 9:54:47 AM
E101 POWER PLANS: could not locate Note 2
02/07/2025 Outdoor Lighting APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 1/29/2025 9:54:47 AM
E101 POWER PLANS: could not locate Note 2
01/23/2025 Water - PDSD APPROVED
02/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/07/2025 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 2/6/2025 12:24:51 AM
1. SHEET S101 - SPECIAL INSPECTIONS: The Statement of Special Inspections included in the structural general
notes, Sheet S101, appears to be incomplete. Please amend the statement to include the following required special inspections per the 2018 International Building Code:
i. Open-Web Steel Joists per the 2018 IBC, Table 1705.2.3.
ii. Post-installed and cast-in-place anchors per the 2018 IBC, Table 1705.3, Items 3 & 4
2. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 1/23/2025 2:53:32 PM
02/07/2025 Commercial Mechanical REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/3/2025 1:50:19 PM
1. General - Provide Heat Load calculations. Show all O/A Ventilation in the load calculations. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
02/07/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/6/2025 9:40:33 PM
First Plumbing Review:'
1). General Plumbing Plans: Missing roof drain conductor illustrations & sizing calculations. Add roof drain conductor
illustrations & sizing calculations. -2018 IPC 1106.1, 1106.2
2). Plan pages P1 & P3: Missing Gray water system detail. Add Gray Water System Detail to the Plumbing Plans. 2018 IPC
301.3
3). Plan Page P-3: Sanitary riser missing 1st floor & 2nd floor Service sink piping illustrations. Add 1st floor & 2nd floor
Service sink piping illustrations.-2018 IPC 106.3.1, 901.2.1
4). Plan Page P-0: Fixture schedule missing Manufacturer names & model numbers for fixtures & water Heater. Add
Manufacturer names & model numbers for fixtures & water Heater to the fixture schedule. -2018 IPC 303
5). Plan Page P-0: 30 Gallon Water Heater appears to be undersized for the demand shown. Provide information that shows
the 30 Gall =on WH will supply enough hot water to all the fixtures. -2018 IPC 607.1
01/23/2025 Site Engineering REQUIRES RESUBMIT 1. Phase 2 of the development package TD-DEV-0223-00144 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
01/24/2025 Site Zoning REQUIRES RESUBMIT See Engineering comments. Additional comments may be forthcoming.
01/15/2025 Fire New Construction REVIEW COMPLETED Fire Alarm and Fire Sprinklers Systems requires a separate submittal and permit.
12/31/2024 PDSD Application Completeness Express REVIEW COMPLETED