Permit Number: TC-COM-1224-02437
Parcel: 13809002E

Address:
5951 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1224-02437
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2025 Commercial Building APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 4/26/2025 11:47:07 AM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 1/23/2025 2:53:32 PM
04/28/2025 Commercial Mechanical APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 4/24/2025 10:49:37 AM
04/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/28/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 4/28/2025 12:49:40 AM
Second Plumbing Review: COMMENT 2 REMAINS
RESOLVED-1). General Plumbing Plans: Missing roof drain conductor illustrations & sizing calculations. Add roof drain
conductor illustrations & sizing calculations. -2018 IPC 1106.1, 1106.2
UNRESOLVED-2). Plan pages P1 & P3: Missing Gray water system detail. Add Gray Water System Detail to the Plumbing
Plans. 2018 IPC 301.3 **SITE PLAN PAGES NOT PROVIDED**
RESOLVED-3). Plan Page P-3: Sanitary riser missing 1st floor & 2nd floor Service sink piping illustrations. Add 1st floor &
2nd floor Service sink piping illustrations.-2018 IPC 106.3.1, 901.2.1
RESOLVED-4). Plan Page P-0: Fixture schedule missing Manufacturer names & model numbers for fixtures & water Heater.
Add Manufacturer names & model numbers for fixtures & water Heater to the fixture schedule. -2018 IPC 303
RESOLVED-5). Plan Page P-0: 30 Gallon Water Heater appears to be undersized for the demand shown. Provide
information that shows the 30 Gall =on WH will supply enough hot water to all the fixtures. -2018 IPC 607.1
04/21/2025 Site Engineering REQUIRES RESUBMIT TC-COM-1224-02437
5951 S 12TH AV

Site engineering comments are as follows:
1. As stated by Zoning, this building permit cannot be approved until the associated Development Package, TD-DEV-0223-00144, is approved by all reviewers.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
04/21/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-1224-02437 - TD-DEV-0223-00144
5951 S 12TH AV. - R-1
Pusch Ridge Christian Academy – South Campus - Phase 2 West Wing Building (2nd Review)

TRANSMITTAL DATE: ‎April 21, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). Educational Use: Elementary & Secondary is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.3.D.1-7.

1. Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0223-00144 and the following comments need to be addressed. Until the DP is approved by all review agencies Zoning cannot approve this permit.

2. Per UDC Article Per UDC Table 6.3-2.A the maximum building height allowed in the R-1 one is 25’. Per UDC Article 6.4.4.A Measurement of Building Height, building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof, except as follows: (See Figure 6.4.4-A, Measurement of Building Height.) As height dimension from design grade were not provide Zoning cannot determine if the building is within the allowed 25’ max. height but based on the dimensions provided on the building elevations the proposed building exceeds the allowed height. A Board of Adjustment for Variance will need to be submitted and approved to exceed the allowed height.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/07/2025 PDSD Application Completeness Express REVIEW COMPLETED