12/16/2024 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-1224-02304 (317 W 23RD ST Unit:BLDG 5 TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).
Outdoor Lighting Code (OLC).


Electrical:
1. Add the following note or an equivalent note regarding the line-side interconnection on the existing bus: Tap must utilize factory installed holes in the bus marked with the word 'TAP'

Outdoor lighting Review:
2. Clarify if any additional under canopy lights are being added.
3. Provide circuiting information for any under-canopy lighting, including conductor, conduit, OCPD and circuit number.
4. Provide disconnect means as required per 225.31- 225.32 for the lighting circuits.
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Full Cut Off fixtures under an overhang or canopy are exempt from the calculation, OLC 4.2.1.