Permit Number: TC-COM-1223-02914
Parcel: 126191910

Address:
4431 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1223-02914
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2024 Water - PDSD APPROVED
01/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/12/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 1/9/2024 8:54:32 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments.

2. GENERAL - SPECIAL INSPECTIONS: Please have the Registered Design Professional in Responsible Charge of this project complete and return the City of Tucson Special Inspections Certificate with signatures. The form can be
downloaded at: https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf

3. S001 - DEFERRED SUBMITTALS: The list of deferred submittals provided in the structural general notes appears to be incomplete. Per the 2018 IBC, Section 106.3.4, “The registered design professional in responsible charge shall list
[all] the deferred submittals on the construction documents for review by the code official.” Please confirm if design of the following items are being deferred or provide a complete design as part of this revision.

i. Steel shade canopies with aluminum perforated panels per A104, Keynote 5.01

ii. Detached structural steel pergola per 3/G111 and L2.2, Keynote 12

iii. Steel solar parking covers (car ports) per G101, Keynote 5.11

4. S001 - DESIGN ASSUMPTIONS: The following structural design information shall be included in the construction documents per 2018 IBC Section 1603. Please include the following items in the structural general notes.

i. Wind design data: Design wind pressures for exterior component and cladding materials expressed in psf

ii. Seismic design data: Seismic design category

5. S001 - TYPICAL WALL SHEATHING: Structural general notes provide information on typical wood structural sheathing thickness and fastening. For walls, the notes refer to the shear wall schedule for more information, however, reviewer could not locate information on the required sheathing and fastening of typical exterior non-shear walls. Please indicate where this information can be located.

6. S002 - MISSING INFORMATION: The Plan Legend on S002 indicates a hatch for an 8" CMU wall around the elevators (plan east, all floors). Please indicate where typical reinforcement has been called out on plan. Reviewer could not locate.

7. S103 - CONFLICTING INFORMATION: The Foundation and Framing Schedules on Sheet S103 provide information that conflicts with the structural calculation package at the following locations. Please revise the schedules to match the calculations or revise the calculations as needed.

i. Typical Column "C1" has been designed with a 3/4" thick base plate (Calculations, Pg 83, 85). The schedule calls out a 3/8" base plate. Please confirm.

ii. Typical Joist "J8" has been designed as a 2x14 member @ 32" oc (Calculations, Pg 38). Schedule calls out a 2x19, which is not a recognized size. Please confirm.

8. S302 - STEEL COLUMNS: Details 235 and 224 cut at the Roof Terrace shade structure call out steel columns with no size indicated on plan. Please confirm that these columns are Typical Column "C1" (HSS5x5x5/16) or provide an alternative size.

9. S402 - MISSING DETAIL: Roof Plan S402 includes a section cut for Detail 313 at the plan-north exterior. Detail 313 does not appear in the typical roof detail Sheet S701.

10. S601/S602/S701 - DESIGN CLARIFICATION: Details 211, 230 and 308 show wood header beams installed flush with the stud wall double top plate. Please confirm that no Simpson strapping is required to maintain continuity where top
plates are being interrupted.

11. S602 - DESIGN CLARIFICATION: Detail 221 shows a wood pony wall installed at the edge of the rooftop terrace that appears to act as fall protection for occupants. Please confirm that this pony wall has been designed for typical out-of plane handrail loads per the 2018 IBC Chapter 16.

12. S602 - MISSING INFORMATION: Details 232 & 233 show a wood-to-steel connection with vertical steel knife plates welded to an HSS column. Please provide the minimum thickness for this knife plate.

13. S701 - PARAPETS: Architectural Elevations on Sheet A201 show a maximum Top of Parapet of approximately 8'-0" measured from Top of Stud Wall Top Plate. Please confirm that these parapets have been accounted for in the design of the main wind force resisting system, and consider adding a maximum parapet height to Details 301 and 302 where parapets are framed with cantilevered 2x6's or built integral with the prefabricated wood trusses. Please note that kickers may be requested by the wood truss manufacturer.

14. S801 - STEEL COLUMN SIZE: Stair #1 Framing Plan and Detail 407 indicates a structural steel column supporting the stair landing. No size has been provided. Please confirm that this column is a Typical Column "C1" (HSS5x5x5/16) or provide an alternative size.

15. S802 - WOOD HANDRAIL DETAIL: Detail 426 calls for a wood handrail with a double 2x4 top plate restrained at either end by a wood stud wall. However, based on the geometry of Stairs #2 and #3 at Level 3, handrail is not continuous from wall to wall, and is interrupted by the descending stairs. Please confirm that this is acceptable, and the top rail does not require two points of restraint in order to resist hand rail loads.




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 1/2/2024 6:58:03 PM
1. Sheet G003: The allowable area increase calculations are incorrect. Therefore, the building exceeds the maximum allowable area. The SM factor can only be used if the building is being protected by an NFPA 13 system. These drawings indicate a NFPA 13R system is being used. Provide a corrected area increase calculation and a structure that does not exceed the maximum allowable area in accordance with 2018 IBC Section 506.2.4 and Table 506.2.

2. Sheet G003: The exception for not enclosing exit access stairways and ramps is being used. However, this exception only applies if a NFPA 13 system is being used. However, these documents indicate that a NFPA 13R system is being used. Enclose the staircase or upgrade the sprinkler system type in accordance with 2018 IBC Section 1019.3.

3. Sheet A104: Roof drainage sizing calculations have not been provided. Provide roof drain sizing calculations to the roof plan in accordance with 2018 IPC Section 1106.1 & 1106.2 & Tucson Amendment Appendix B rates of rainfall.

4. Sheet A104: GPM discharge amounts have not been provided for the roof/drain overflows. Provide the roof/drain overflows in accordance with 2018 IPC Section 1106.2

5. Sheet A111: The RCP for the first floor plan does not indicate the location of egress lighting. Provide the location of all egress illumination in accordance with 2018 IBC Section 1008.

6. Sheet A111: The RCP for the first floor plan does not indicate the location of exit lighting. Provide the location of all exit lighting in accordance with 2018 IBC Section 1013.

7. Sheet A112: The RCP for the second floor plan does not indicate the location of egress lighting. Provide the location of all egress illumination in accordance with 2018 IBC Section 1008.

8. Sheet A112: The RCP for the second floor plan does not indicate the location of exit lighting. Provide the location of all exit lighting in accordance with 2018 IBC Section 1013.

9. Sheet A113: The RCP for the third floor plan does not indicate the location of egress lighting. Provide the location of all egress illumination in accordance with 2018 IBC Section 1008.

10. Sheet A113: The RCP for the third floor plan does not indicate the location of exit lighting. Provide the location of all exit lighting in accordance with 2018 IBC Section 1013.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/8/2024 11:47:56 AM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 1/4/2024 4:22:01 PM
Electrical Review of Newport Belvedere Terrace
By: Ron Ross PE
E104 PANEL SCHEDULES: Review revise Series rated design for EVA and EVB panels. 22/10 KAIC series rated is not sufficient.

E211 TYP 1 BR UNIT A+C ENL. POWER AND LIGHT PLAN: Suggestion only. It is common practice to provide a full size refrigerator with a dedicated circuit.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 1/10/2024 12:38:10 AM
First Plumbing Review:
1). All Hose bibs on plan page P101 need shut off valves -IPC 606.2

2). Roof deck on plan page A102 doesn't illustrate the required secondary scuppers as stated on plan page P102. -IPC 1108

3). Exterior Drinking fountain on plan page P101 needs to be protected from receiving rainwater into drain. -IPC 1101.3
01/18/2024 Fire New Construction REQUIRES RESUBMIT -Resolve building comments.
-Include two way communication at elevator lobbies per IFC 1009.8
john.vincent@tucsonaz.gov
5203495581
01/24/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
12/29/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T TC-COM-1223-02914 - TD-DEV-1223-00480
4431 E 22ND ST. – C-2/R-1
Multifamily (1st Review)

TRANSMITTAL: December 29, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-2 zone (UDC 4.7.21), Multifamily is a permitted use in the zone.

1. As Development Package (DP) TD-DEV-1223-00480 has not yet completed the 1st review Zoning cannot compare the plans for compliance with each other. Zoning will review the building plans on the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/26/2023 PDSD Application Completeness REVIEW COMPLETED