Permit Number: TC-COM-1223-02914
Parcel: 126191910

Address:
4431 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1223-02914
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/10/2025 9:07:34 PM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/11/2025 10:23:57 AM
03/03/2025 Site Zoning Standard APPROVED
03/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/12/2025 10:46:54 AM
1. Condition - As per Revision Narrative Letter M001 and M002 - Many of the buildings mechanical systems are updated
or reconfigured • Reference sheet M001 note that mechanical suppliers were unable to provide information on new
equipment, so the updates on M001 show current refrigerant equipment of the correct sizing, type, and configuration.
Mechanical subcontractor will need to identify substitutions for equipment using new refrigerant once available. When
the information becomes available, provide revision. Show in revision all Design equipment information.
2. Plan Sheet M200 - Dryer and Kitchen exhaust must be routed to exterior of building in dedicated ducts. - 2018 IMC
Section 505.3 Exhaust ducts.
03/05/2025 Fire New Construction Standard REVIEW COMPLETED
02/10/2025 PDSD Application Completeness Express REVIEW COMPLETED