Permit Number: TC-COM-1223-02914
Parcel: 126191910

Address:
4431 E 22ND ST

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1223-02914
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2024 Site Zoning APPROVED
05/30/2024 Bldg Permits - Post Review REVIEW COMPLETED
05/30/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 3/29/2024 12:18:37 AM
GENERAL - DEFERRED SUBMITTAL REQUIREMENTS: The engineer of record has indicated that design of the prefabricated wood trusses and steel solar parking covers (carports) will be submitted as a Deferred Submittal. Please note that IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official. The IBC further requires the following procedure be followed when permitting deferred submittals:

1. All submittals shall first be reviewed by design professional in responsible charge.

2. Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.

3. They shall then be submitted for review by the building official.

4. No structural elements shall be installed until approved by building official.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/25/2024 11:45:43 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 1/8/2024 11:47:56 AM


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/22/2024 10:53:30 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/29/2024 9:54:37 PM
T Plumbing Review:OK Subject to field inspections
RESOLVED-1). All Hose bibs on plan page P101 need shut off valves -IPC 606.2

RESOLVED-2). Roof deck on plan page A102 doesn't illustrate the required secondary scuppers as stated on plan page P102. -IPC 1108

OK Per Building Official Letter Attached)...3). Exterior Drinking fountain on plan page P101 needs to be protected from receiving rainwater into drain. -IPC 1101.3**** DESIGNER Response: = Communication has been initiated with the Tucson
Building Official Clayton Trevillyan (clayton.trevillyan@tucsonaz.gov) to accept the minimal amount of rainwater which would enter the sanitary sewer from the water cooler
04/25/2024 PDSD Application Completeness REVIEW COMPLETED