Permit Number: TC-COM-1223-02769
Parcel: 124130260

Address:
502 S FREMONT AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-1223-02769
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/04/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 3/4/2025 12:41:57 AM

Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 3/4/2025 12:43:56 AM
A complete set of drawings is required for approval, not just the sheets that were revised. Please provide a complete set
containing all of the sheets in the set.


Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 3/4/2025 12:39:58 AM



Electrical(E) Reviewer (from previous submittal TUC9660001.012925)
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2025 3:31:10 AM



Plumbing(P) Reviewer (from previous submittal TUC9660001.012925)
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2025 3:30:11 AM
02/26/2025 Fire New Construction REQUIRES RESUBMIT Make corrections as follows:
1.General Building Summary states R-2 which is corrected.
2. Occupant Load and Exiting section states that the project is an R-3 Occupancy. Make corrections and check code references and table and add proper code reference sections.
03/07/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-COM-1223-02769 - TD-DEV-1223-00472
502 S FREMONT AV. – R-3
Multifamily (4th Review)

TRANSMITTAL DATE: March 7, 2025

Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-3 zone (UDC 4.7.12). Multifamily is a permitted use in this zone (Table 4.8-2). See Use-Specific Standard 4.9.7.B.6

1. Until DP TD-DEV-1223-00472 is approved by all review agencies Zoning cannot approved this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/10/2025 Water - PDSD REQUIRES RESUBMIT Provide a complete set of drawings for approval.
02/24/2025 PDSD Application Completeness Express REVIEW COMPLETED