Permit Number: TC-COM-1222-00337
Parcel: 11504495A

Address:
1001 N PARK AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00337
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2023 Site Engineering APPROVED See Zoning Comment
08/24/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/11/2023 Design Review REQUIRES RESUBMIT The set of construction documents must match the set of plans included in the second modification of the Design Package, as approved by the PDSD Director on 5/10/23, under Activity # SD-0523-00048.
08/24/2023 External Reviewers - Stantec REQUIRES RESUBMIT APPROVAL RECEIVED FROM THE 3RD PARTY REVIEWER - Applicant to upload the latest set of plans and documents which include comment updates from all reviewers, including the 3rd Party Reviewer, through the TDC-Online@tucsonaz.gov".
01/30/2023 Fire New Construction REQUIRES RESUBMIT Deferred submittals:
Smoke control
Fire sprinkler
Fire alarm
Emergency Responder Radio Coverage
Above Ground Storage tank
Flammable and Combustible Liquids
Places of Assembly

Plans shall show the requirements of IBC 2018, Chapter 4. Section 403.3.3 are being met on sheet G0.03
Sheet G0.03 Chapter 9 - 911 Fire Command Center 911.1.3 shows 200 sq ft shall be 369.6 sq feet.
Sheet G0.03 Chapter 9 - Add standpipe requirements in accordance with 905
Sheet G0.03 Chapter 10 - Add note: Two-way communication compliant with 1009.8
Sheet G0.04 Chapter 30 - Add note: Elevator compliant with 3001.2
Sheet G0.04 under elevators 3007.1 States where required by Section 503.6.1 - that section does not exist should be 403.6.1
Note shall be added: Elevator Monitoring System shall be compliant with IBC 2018, Chapter 30, Section 3007.7
S2.08 shall include detail and comments regarding the elevator Hoist way brace/support beam and show that it is OSHA and manufacturer compliant for weight and tying off - To be determined is not acceptable.
Plumbing sheets show how the generator gets fueled.
Electrical plans show smokes and a note 18 Line-voltage smoke detector. All detectors shall alarm together. One detector in hallway or living room shall be combination smoke/carbon monoxide detector - We have a modification that requires that they be fire alarm system smoke detectors
Add notes: KNOX Boxes, Elevator KNOX box, KNOX Key switch and locking KNOX F.D.C. caps shall be provided by owner

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/10/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1222-00337
1001 N Park Ave. – UC-1
Residential – Group Dwelling (1st Review)

TRANSMITTAL: January 10, 2023
This site is located in UC-1 Zone (UDC 4.7.20) & Main Gate UOD. Residential – Group Dwelling is a permitted use in the zone (Table 4.8-4) and overlay.

1. Zoning has reviewed the building plans for compliance with Development Package DP20-0152 and although it appears that the plans match until the building plan is approved by the design professional Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/27/2022 PDSD Application Completeness REVIEW COMPLETED