Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1222-00337
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2023 | Site Engineering | APPROVED | See Zoning Comment | ||
08/24/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/11/2023 | Design Review | REQUIRES RESUBMIT | The set of construction documents must match the set of plans included in the second modification of the Design Package, as approved by the PDSD Director on 5/10/23, under Activity # SD-0523-00048. | ||
08/24/2023 | External Reviewers - Stantec | REQUIRES RESUBMIT | APPROVAL RECEIVED FROM THE 3RD PARTY REVIEWER - Applicant to upload the latest set of plans and documents which include comment updates from all reviewers, including the 3rd Party Reviewer, through the TDC-Online@tucsonaz.gov". | ||
01/30/2023 | Fire New Construction | REQUIRES RESUBMIT | Deferred submittals: Smoke control Fire sprinkler Fire alarm Emergency Responder Radio Coverage Above Ground Storage tank Flammable and Combustible Liquids Places of Assembly Plans shall show the requirements of IBC 2018, Chapter 4. Section 403.3.3 are being met on sheet G0.03 Sheet G0.03 Chapter 9 - 911 Fire Command Center 911.1.3 shows 200 sq ft shall be 369.6 sq feet. Sheet G0.03 Chapter 9 - Add standpipe requirements in accordance with 905 Sheet G0.03 Chapter 10 - Add note: Two-way communication compliant with 1009.8 Sheet G0.04 Chapter 30 - Add note: Elevator compliant with 3001.2 Sheet G0.04 under elevators 3007.1 States where required by Section 503.6.1 - that section does not exist should be 403.6.1 Note shall be added: Elevator Monitoring System shall be compliant with IBC 2018, Chapter 30, Section 3007.7 S2.08 shall include detail and comments regarding the elevator Hoist way brace/support beam and show that it is OSHA and manufacturer compliant for weight and tying off - To be determined is not acceptable. Plumbing sheets show how the generator gets fueled. Electrical plans show smokes and a note 18 Line-voltage smoke detector. All detectors shall alarm together. One detector in hallway or living room shall be combination smoke/carbon monoxide detector - We have a modification that requires that they be fire alarm system smoke detectors Add notes: KNOX Boxes, Elevator KNOX box, KNOX Key switch and locking KNOX F.D.C. caps shall be provided by owner Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
01/10/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-1222-00337 1001 N Park Ave. – UC-1 Residential – Group Dwelling (1st Review) TRANSMITTAL: January 10, 2023 This site is located in UC-1 Zone (UDC 4.7.20) & Main Gate UOD. Residential – Group Dwelling is a permitted use in the zone (Table 4.8-4) and overlay. 1. Zoning has reviewed the building plans for compliance with Development Package DP20-0152 and although it appears that the plans match until the building plan is approved by the design professional Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
12/27/2022 | PDSD Application Completeness | REVIEW COMPLETED |