Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1125-02157
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 12/18/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 12/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/08/2025 | Addressing Validation | REQUIRES RESUBMIT | Unable to process. The address on the uploaded site plan is incomplete. It appears that there are multiple addresses associated with the address 910 W IRVINGTON RD. Please submit a change of address request to add Unit number to the permit location and ensure it matches the unit listed in the construction plans. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions please contact Building_Official@tucsonaz.gov |
||
| 12/26/2025 | Commercial Building Standard | REQUIRES RESUBMIT | December 26, 2025 1st Review Social Partners LLC. Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: IRVINGTON DISPENSARY TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1125-02157 Stantec Project Number: 185215066 Stantec File Number: TUC-25-111 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 5,145 278 Yes No Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: Signage. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Sheet A402 1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS General 1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/26/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | December 26, 2025 1st Review Social Partners LLC. Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: IRVINGTON DISPENSARY TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1125-02157 Stantec Project Number: 185215066 Stantec File Number: TUC-25-111 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 5,145 278 Yes No Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: Signage. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Sheet A402 1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS General 1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/26/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | December 26, 2025 1st Review Social Partners LLC. Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: IRVINGTON DISPENSARY TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1125-02157 Stantec Project Number: 185215066 Stantec File Number: TUC-25-111 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 5,145 278 Yes No Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: Signage. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Sheet A402 1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS General 1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/26/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | December 26, 2025 1st Review Social Partners LLC. Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: IRVINGTON DISPENSARY TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-1125-02157 Stantec Project Number: 185215066 Stantec File Number: TUC-25-111 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 5,145 278 Yes No Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: Signage. Special Inspections: None. ARCHITECTURAL COMMENTS General 1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). Sheet A402 1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS General 1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604] ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 12/30/2025 | Site Zoning Standard | REQUIRES RESUBMIT | Final Site Zoning approval of this permit cannot be provided until the associated development package, TD-DEV-1125-00297, is first approved. Please ensure that changes to any plans on the development package are reflected on this permit. Specifically, on sheet A111 (floor plan) graphically indicate that it meets the requirements of Special Exception condition #9: “An interior customer waiting area of at least 25 percent of the sales floor area shall be provided.” Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov. |
||
| 12/23/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | Provide the size of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
| 12/30/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 12/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |