Permit Number: TC-COM-1125-02157
Parcel: 120052730

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1125-02157
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/18/2025 Site Engineering Standard NOT REQUIRED
12/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/08/2025 Addressing Validation REQUIRES RESUBMIT Unable to process. The address on the uploaded site plan is incomplete. It appears that there are multiple addresses associated with the address 910 W IRVINGTON RD. Please submit a change of address request to add Unit number to the permit location and ensure it matches the unit listed in the construction plans.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

For questions please contact Building_Official@tucsonaz.gov
12/26/2025 Commercial Building Standard REQUIRES RESUBMIT December 26, 2025
1st Review

Social Partners LLC.
Attn: Andrew Kevelson
4847 N. Louis River Way
Tucson, Arizona 85718

Re: IRVINGTON DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1125-02157
Stantec Project Number: 185215066
Stantec File Number: TUC-25-111

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 5,145 278 Yes No
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Signage.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet A402

1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/26/2025 Commercial Electrical Standard REQUIRES RESUBMIT December 26, 2025
1st Review

Social Partners LLC.
Attn: Andrew Kevelson
4847 N. Louis River Way
Tucson, Arizona 85718

Re: IRVINGTON DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1125-02157
Stantec Project Number: 185215066
Stantec File Number: TUC-25-111

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 5,145 278 Yes No
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Signage.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet A402

1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/26/2025 Commercial Mechanical Standard REQUIRES RESUBMIT December 26, 2025
1st Review

Social Partners LLC.
Attn: Andrew Kevelson
4847 N. Louis River Way
Tucson, Arizona 85718

Re: IRVINGTON DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1125-02157
Stantec Project Number: 185215066
Stantec File Number: TUC-25-111

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 5,145 278 Yes No
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Signage.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet A402

1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/26/2025 Commercial Plumbing Standard REQUIRES RESUBMIT December 26, 2025
1st Review

Social Partners LLC.
Attn: Andrew Kevelson
4847 N. Louis River Way
Tucson, Arizona 85718

Re: IRVINGTON DISPENSARY
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1125-02157
Stantec Project Number: 185215066
Stantec File Number: TUC-25-111

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 5,145 278 Yes No
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Signage.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet A402

1. The accessible restrooms do not include a vertical grab bar at the side wall of the water closet. Please provide. [Ref. ICC A117.1-2009 Sec. 604.5.1]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide an updated calculation for the water pressure drop from the service to the last remote fixture having the most demanding pressure. [Ref. IPC 2018 Sec. 604]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
12/30/2025 Site Zoning Standard REQUIRES RESUBMIT Final Site Zoning approval of this permit cannot be provided until the associated development package, TD-DEV-1125-00297, is first approved. Please ensure that changes to any plans on the development package are reflected on this permit.

Specifically, on sheet A111 (floor plan) graphically indicate that it meets the requirements of Special Exception condition #9: “An interior customer waiting area of at least 25 percent of the sales floor area shall be provided.”

Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov.
12/23/2025 Water - PDSD Standard REQUIRES RESUBMIT Provide the size of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
12/30/2025 Fire New Construction Standard REVIEW COMPLETED
12/08/2025 PDSD Application Completeness Express REVIEW COMPLETED