Permit Number: TC-COM-1026-01750
Parcel: 13817032B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1026-01750
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/23/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions, please contact cdrc@tucsonaz.gov

A separate trade permit is required for each unit. Sub-panel replacement in separate apartments requires one permit for each unit. This trade permit can be for 330 E CORONA RD UNIT 3101. Please apply for a separate permit for each of the other 4 units.

A change of address request is required to remove all addresses from this permit that are not 330 E CORONA RD UNIT 3101.

Once that is complete, please resubmit documents to this permit.

Instructions can be found here to request change of address: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf
10/23/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review
TC-COM-1026-01748
TC-COM-1026-01749
TC-COM-1026-01750
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Clarify if the main service ‘Package Panel’ is also being replaced.
2. Provide Service Surge Protection per NEC 230.67(D). All downstream dwelling units require surge protection when replacing the service equipment.
3. Provide the rating of the sub-panels.
10/23/2026 PDSD Application Completeness Express REVIEW COMPLETED