Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1024-02026
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/01/2024 | Commercial Building | REQUIRES RESUBMIT | SAME SET OF PLANS: TC-COM-1024-02023, TC-COM-1024-02024, TC-COM-1024-02025,TC-COM-1024-02026 Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. 1. Provide an evaluation from an Arizona licensed design professional to indicate the existing roof structure can support the new RTU to include calculations, plans/details for the support of such equipment as needed. IBC 107.2.1 Alternatively, provide the weight of existing Evaporative Cooler to be removed and a comparison to the new RTU’s weight. If the new RTU weighs less than the existing, removed RTU all is good Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 11/06/2024 | Commercial Electrical | REQUIRES RESUBMIT | SAME SET OF PLANS: TC-COM-1024-02023, TC-COM-1024-02024, TC-COM-1024-02025,TC-COM-1024-02026 Please address the electrical plan review comments and provide a written response. 1 This project is categorized as commercial. Please revise all references to the IRC to the 2017 NEC. REF; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 11/06/2024 | Commercial Mechanical | REQUIRES RESUBMIT | SAME SET OF PLANS: TC-COM-1024-02023, TC-COM-1024-02024, TC-COM-1024-02025,TC-COM-1024-02026 Verify the capacity of the proposed heat pump: the specified cooling capacity is less than half of the capacity identified by the cooling/heating load calculations. Reference: Section R403.7, IECC 2018. |
||
| 10/23/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |