Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0925-01647
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/10/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0925-01647 (702 E 17TH ST TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Note on the plans and show compliance with NEC 750 for Energy Management Systems. Including required Field Markings that show the following information: (1) Maximum current setting (2) Date of calculation and setting (3) Identification of loads and sources associated with the current limiting feature (4) The following or equivalent wording: "The setting for the EMS current limiting feature shall not be bypassed" Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/09/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |