Permit Number: TC-COM-0825-01545
Parcel: 13213104B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0825-01545
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2025 Site Zoning Standard NOT REQUIRED
09/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/10/2025 Commercial Building Standard REQUIRES RESUBMIT Alteration level 3 commercial fee
08/27/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0825-01545 (3300 S PARK AV Unit:BLDG 2 TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Each building or structure shall be supplied by a single branch circuit or feeder, NEC 225.30.
2. Provide a grounding electrode on the Riser Diagram the sub-panel, and each separate building or structure supplied by feeders or branch circuits, NEC 250.32.
3. Provide a disconnecting means at each building or structure where the branch circuits or feeders enter the buildings, per NEC 225.30 & 225.32.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/27/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0825-01545 (3300 S PARK AV Unit:BLDG 2 TUCSON, AZ 85713)

1. Provide manufacture’s specification sheets for outdoor lighting fixtures showing full cutoff status.
09/05/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0825-01545
Location: 3300 S Park AV
Review Date: 9/5/2025
Site Engineering Comments:
1. Site Engineering will be unable to approve permit TC-COM-0825-01545 until the associated Development Package TD-DEV-0825-00212 has been reviewed and approved by all reviewers.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
09/04/2025 Fire New Construction Standard REVIEW COMPLETED
08/18/2025 PDSD Application Completeness Express REVIEW COMPLETED