Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0824-01675
Parcel: 10709007C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0824-01675
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2024 Commercial Mechanical APPROVED
09/16/2024 Commercial Plumbing APPROVED
09/30/2024 Site Engineering APPROVED
09/27/2024 Site Zoning APPROVED
09/26/2024 Water - PDSD APPROVED
09/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/16/2024 Commercial Electrical REQUIRES RESUBMIT September 16, 2024
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Rd.
Tucson, Arizona 85710

Re: TEEN CHALLENGE – BLDG. 3 ADMINISTRATION
SHELL, CORE, FITOUT

City of Tucson Permit Number: TC-COM-0824-01675
Stantec Project Number: 185215066
Stantec File Number: TUC-24-126

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,244 74 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate on the cover page that the fire alarm system [2018 IBC Sec. 907] and metal canopy structure will be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet GA101

1. Please indicate the permit number the site lighting is being applied for under on this sheet. {This comment was also included under the Electrical Comments section.}

Sheet A111

1. The plans indicate 1 accessible bathroom out of 3 provided. At least 50% of single-user toiler rooms must be accessible. Please revise. [Ref. IBC 2018 Sec. 1109.2 exc. 3]

Sheet A121

1. Please provide roof access. [Ref. IBC 2018 Sec. 1011.12.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide on the plans complete outdoor lighting calculations showing compliance with the 2012 City of Tucson/Pima County Outdoor Lighting Code (OLC) on the plans which include the following information:
a. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded, and the color rendition (i.e. not to exceed 3500K).
b. The total of full cut-off and unshielded lumens for the parcel.
c. A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens.
d. A statement that special inspection is required (or is not required) per Sec. 104.2.2.
{Please provide a note on the plans if the exception from Section 104.2.1 is being met}

2. Please indicate the permit the site lighting is being applied for under on the site plan.

3. Please provide an energy conservation compliance report for exterior lighting. [Ref. IECC 2018 Sec. C405.4]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/16/2024 Commercial Structural REQUIRES RESUBMIT September 16, 2024
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Rd.
Tucson, Arizona 85710

Re: TEEN CHALLENGE – BLDG. 3 ADMINISTRATION
SHELL, CORE, FITOUT

City of Tucson Permit Number: TC-COM-0824-01675
Stantec Project Number: 185215066
Stantec File Number: TUC-24-126

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,244 74 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate on the cover page that the fire alarm system [2018 IBC Sec. 907] and metal canopy structure will be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet GA101

1. Please indicate the permit number the site lighting is being applied for under on this sheet. {This comment was also included under the Electrical Comments section.}

Sheet A111

1. The plans indicate 1 accessible bathroom out of 3 provided. At least 50% of single-user toiler rooms must be accessible. Please revise. [Ref. IBC 2018 Sec. 1109.2 exc. 3]

Sheet A121

1. Please provide roof access. [Ref. IBC 2018 Sec. 1011.12.2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. Please provide on the plans complete outdoor lighting calculations showing compliance with the 2012 City of Tucson/Pima County Outdoor Lighting Code (OLC) on the plans which include the following information:
a. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded, and the color rendition (i.e. not to exceed 3500K).
b. The total of full cut-off and unshielded lumens for the parcel.
c. A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens.
d. A statement that special inspection is required (or is not required) per Sec. 104.2.2.
{Please provide a note on the plans if the exception from Section 104.2.1 is being met}

2. Please indicate the permit the site lighting is being applied for under on the site plan.

3. Please provide an energy conservation compliance report for exterior lighting. [Ref. IECC 2018 Sec. C405.4]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/26/2024 Fire New Construction REVIEW COMPLETED
08/29/2024 PDSD Application Completeness REVIEW COMPLETED