Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0824-01536
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/06/2024 | Commercial Electrical | APPROVED | |||
09/06/2024 | Commercial Mechanical | APPROVED | |||
09/06/2024 | Commercial Plumbing | APPROVED | |||
09/05/2024 | Site Zoning | APPROVED | |||
09/09/2024 | Site Engineering | NOT REQUIRED | |||
09/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/06/2024 | Commercial Structural | REQUIRES RESUBMIT | For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or by cell (928)580-3179. All applicable comments followed by the initials (BM) 1. Sheet A1.2 Identify if existing exit hallway is a rated corridor or interior exit stairway. Interior exit stairways shall not be used for any purpose other than a means of egress and circulation path to required exit 2018 IBC 1023.1. Room 208 access needs to be addressed. (BM) 2. Sheet A1.2 Clarify if new door 203.1 will need to be a rated door and frame to comply with corridor and interior stairway rating per 2018 IBC 1023.2 & 1020.1 (BM) |
||
09/09/2024 | Fire New Construction | REQUIRES RESUBMIT | -Resolve building comments. john.vincent@tucsonaz.gov 5203495581 |
||
08/07/2024 | PDSD Application Completeness | REVIEW COMPLETED |