Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0726-01164
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2026 | Commercial Electrical | APPROVED | |||
| 08/07/2026 | Commercial Plumbing | APPROVED | |||
| 08/07/2026 | Water - PDSD | APPROVED | |||
| 08/07/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/06/2026 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01164 ADDRESS/PARCEL: (7090 E 22ND ST TUCSON, AZ 85710) TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. NEW HOOD a. Provide structural detail drawings as to how the Hood and the Grease Duct are supported, this also applies to the upblast exhaust fan on the roof as well as the weight of personnel working in or on the hood such as during hood cleaning. i. Provide Structural Calculation for the items listed above. ii. Both drawings and calculations above must bear the structural engineer’s seal/signature/date signed. 2. SHEET MP2.0 a. Keyed Notes #14: Please correct the use of combustible for the hood installation. It should be non-combustible. b. Add a note indicating the use of metal studs on the non-combustible wall per IMC 507.2.4. 3. Please resubmit. |
||
| 08/07/2026 | Commercial Mechanical | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01164 ADDRESS/PARCEL: 7090 E 22ND ST TUCSON, AZ 85710 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please provide an air balance schedule showing the total supply and exhaust airflow quantities for the building. Demonstrate that the proposed HVAC systems maintain the 150 CFM net positive building pressure. Reference: Section 508.1.3, IMC 2024. |
||
| 08/05/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 07/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |