Permit Number: TC-COM-0723-01809
Parcel: 140240250

Address:
1200 E BILBY RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0723-01809
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/02/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The site plan submitted does not correlate with the electrical plan. It appears the scope of work entered in details states “Like for like wire replacement.wire replacement inside the gutter”. The site plan shows an electrical service at one location and 3- 200 amp boxes.

This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
07/26/2023 PDSD Application Completeness REVIEW COMPLETED