Permit Number: TC-COM-0626-00869
Parcel: 30501005A

Address:
10000 S RITA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00869
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2026 Landfill Standard NOT REQUIRED Project location is not within the 100-ft or 500-ft boundary to Rita Road Landfill, thus the Landfill Review is not required.
07/09/2026 Water - PDSD Standard NOT REQUIRED Tucson Water review is not required for this project, as the proposed water supply is provided by an existing private water well and no connection to the Tucson Water system is proposed.
07/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/09/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Sheet C-0: Code Review -Please revise the 2028 IECC edition reference. The 2018 was being enforced when this permit was applied for. IBC 107.2.1
2. Sheet C-0: 2024 IBC Review -Please provide Occupancy use under the Storage Group as A is not available in the IBC. For example, S-2. IBC Section 311
3. Sheet C-0: 2024 IBC Review -Please revise the allowable area to match IBC Table 506.2 For example if this is an S-2 use non-sprinklered type IIB construction, the allowable area would be 26000 SF
4. Sheet A-3: Cross Section “A”- Please provide architectural and structural construction drawings, details, and structural calculations for Keynote 29 – Air Handler on Interior Roof, as indicated on the mechanical plans, in accordance with 2024 IBC Sections 107.2.1 and 107.2.7.
Additionally, coordinate the architectural, structural, and mechanical drawings, as the mechanical plans depict the air handler suspended below the ceiling framing, which conflicts with Keynote 29.
5. Sheet A-5: Floor Plan – Please revise plan to show and callout a 67” turning space, as 2017 ICC A117.1 [304.3.1.1] New buildings and facilities. In new buildings and facilities, the turning space shall be a circular space with a 67-inch minimum diameter.
6. Sheet A-5: Interior Elevation “A” – Please revise drawing or otherwise indicate 603.3 Mirrors. Where mirrors are located above lavatories, a mirror shall be located over the lavatory complying with Section 606 and shall be mounted with the bottom edge of the reflecting surface 40 inches maximum above the floor.
7. Structural Foundation Drawing sheet 2 of 2 - Please revise the list of required special inspections to include 2024 IBC 1705.2.6 Metal Building Systems special inspection and it’ schedule of special inspections. IBC 107.2.1

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/08/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00869 (10000 S RITA RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a Grounding Electrode System at the detached structure per 250.31(A). Grounding electrode system and grounding electrode conductor. Required.
250.31(A) Grounding electrode system and grounding electrode conductor. Required.
250.31(B) equipment grounding conductor, grounding bonding equipment and structural metal. Sized accordance with 250.122.
2. Notate the grounding and bonding method, including water line bonding, NEC 250.20(B), 250.24, 250.30(A)(1).
3. Provide appropriate grounding and bonding of all metal structures, per all relevant sections of NEC 250 (example sections 250.4(A), 250.20, 250,32, 250.104).
4. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck.)
07/09/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00869
ADDRESS/PARCEL: 10000 S RITA RD TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide heating and cooling load calculations to justify the heating/cooling capacity of the Split System Heat Pump. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
07/09/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00869
ADDRESS/PARCEL: 10000 S RITA RD TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide roof drainage calculations, including gutter/downspout sizing and gutter slope, based on the 100-year hourly rainfall rate for Tucson, 3” per hour. Reference: Sections 1101.7, 1106, and 1108, IPC 2024.
2. The plans show a proposed private water line and septic system improvements that are not included in the approved development plan (TD-DEV-0723-00309). Please update the development plan to incorporate these proposed utility changes.
07/07/2026 Entitlements Standard REQUIRES RESUBMIT This should be submitted as a revision to the existing Development Package TD-DEV-0723-00309. A modification request must also be submitted to modify the Preliminary Development Plan established in Rezoning TP-ENT-0323-00018. Outdoor lighting must demonstrate conformance to condition 19 of the rezoning case.
07/08/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0626-00869 (10000 S RITA RD TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Outdoor lumen Calculations are incomplete. Show all 6 W1 lighting fixtures in the calculations and show lighting fixture P1 in the calculations.
Clarify why the two existing fixtures are shown with a negative lumen value. Are they being removed from the site? If so, show a basic demo sheet of the removal.
07/10/2026 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TC-COM-0626-00869
10000 S RITA RD

Permit Summary: Construction of a 60' x 40' pre-engineered metal building (PEMB) including office build-out and a restroom, along with associated site improvements such as grading and utilities.

Site Engineering comments are as follows:

1. The proposed building and site improvements will require a revision to the Associated Development Package, TD-DEV-0723-00309. The revision to the DP must be approved by all reviewers prior to the approval of this Commercial Building Permit. AM 2-06.2.3

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
07/07/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0626-00869 - TD-DEV-0723-00309
10000 S. Rita Rd. Tucson, AZ 85747
New 60’x40’ Prefab Metal Building, Restroom, Site Improvements (1st Review)

TRANSMITTAL DATE: 7/7/2026

This site is located in the I-1 zone (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: A new building and associated parking/site improvements are being proposed with this permit however the associated Development Package (TD-DEV-0723-00309) does not reflect these improvements. Please revise TD-DEV-0723-00309 to show these new site improvements. Site zoning is unable to approve this permit until TD-DEV-0723-00309 has been revised and approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED