Permit Number: TC-COM-0625-01252
Parcel: 12315031B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0625-01252
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2025 Commercial Mechanical REQUIRES RESUBMIT ADDRESS/PARCEL: 715 E LEE ST TUCSON, AZ 85719 (Unit #: 3, 5, 6, 9, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 24, 27, 28)
The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. The drawing needs to include local exhaust systems and mechanical ventilation systems for outdoor air that meet the requirements of IMC 403.3.2 since you are replacing an Evaporative Cooler with a Packaged Gas/ Electric Unit. Please revise to demonstrate compliance with the ventilation and exhaust rates required.