Permit Number: TC-COM-0625-01237
Parcel: 12315031B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0625-01237
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2025 Commercial Building APPROVED
07/02/2025 Commercial Electrical APPROVED
07/15/2025 Commercial Plumbing APPROVED
07/15/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2025 Commercial Mechanical REQUIRES RESUBMIT 1. The plans were sealed 2/24/2020. Provide a current seal for the next submittal.
2. The specified rooftop units are not heat pumps, they have gas-fired furnaces, and they are no longer available for sale. Correct the specifications with a current product that has a SEER2 efficiency rating. Reference: Section 107.2.1, IBC 2018.
07/01/2025 PDSD Application Completeness Express REVIEW COMPLETED