Permit Number: TC-COM-0525-00978
Parcel: 10709007C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0525-00978
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2025 Outdoor Lighting APPROVED
06/06/2025 Site Engineering APPROVED
06/02/2025 Site Zoning APPROVED
06/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/02/2025 Commercial Building REQUIRES RESUBMIT June 2, 2025
1st Review

Light+Path Architecture LLC
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE MENS CENTER
NEW EXTERIOR CANOPY

City of Tucson Permit Number: TC-COM-0525-00978
Stantec Project Number: 185215066
Stantec File Number: TUC-25-056

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
U V-B 1,408 8 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, field welding, cold-formed steel deck.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

Sheet S3.0

1. Detail 601 refers to a “Typical Bolt Schedule” for size, type and number of bolts. The plans do not appear to contain a schedule for this. Please clarify.
2. Detail 611 appears to be missing a dimension between the steel beams. Also, please clarify the symbols at the steel roof deck of this detail.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/02/2025 Commercial Electrical REQUIRES RESUBMIT June 2, 2025
1st Review

Light+Path Architecture LLC
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE MENS CENTER
NEW EXTERIOR CANOPY

City of Tucson Permit Number: TC-COM-0525-00978
Stantec Project Number: 185215066
Stantec File Number: TUC-25-056

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
U V-B 1,408 8 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, high-strength bolts, field welding, cold-formed steel deck.

ARCHITECTURAL COMMENTS

There are no comments.

STRUCTURAL COMMENTS

Sheet S3.0

1. Detail 601 refers to a “Typical Bolt Schedule” for size, type and number of bolts. The plans do not appear to contain a schedule for this. Please clarify.
2. Detail 611 appears to be missing a dimension between the steel beams. Also, please clarify the symbols at the steel roof deck of this detail.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/15/2025 PDSD Application Completeness Express REVIEW COMPLETED