Permit Number: TC-COM-0425-00797
Parcel: 14044004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00797
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/1/2025 8:14:08 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/6/2025 2:10:38 PM
05/08/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/5/2025 8:34:20 AM
05/08/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 5/8/2025 10:04:38 PM
05/08/2025 Outdoor Lighting Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/5/2025 8:34:20 AM
05/16/2025 Site Engineering Standard APPROVED
05/15/2025 Site Zoning Standard APPROVED
05/14/2025 Water - PDSD Standard APPROVED
05/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/08/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 5/6/2025 5:46:55 PM
1. General - Include in the Ventilation schedule on Plan Sheet M-002 the warehouse area. Specify on the drawings the
outdoor air required by the 2018 IMC Section 403.3.1.1 Substantiate compliance by providing calculations on the
drawings which indicates the floor area (sq. ft), maximum occupant load, minimum required ventilation rate (cfm) for
each occupancy, and total ventilation rate provided to the occupied space.
2. General - Provide in the Mechanical section plan sheets the warehouse area. Show all intake louvers, exhaust fans. -
2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on
construction documents.
05/13/2025 Fire New Construction Standard REVIEW COMPLETED Any alterations to the fire alarm or fire sprinklers requires a separate submittal and permit. Fire extinguishers shall comply with section 906 of the 2018 IFC
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED