Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0425-00796
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2025 | Commercial Building | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 7/5/2025 6:12:42 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 7/9/2025 10:02:41 AM |
||
| 07/11/2025 | Commercial Electrical | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 7/3/2025 10:42:01 AM 1. IE113 ENLARGED OFFICE HVAC PLAN: Should have provided circuit information for bathroom power. 2. IE311: Should have performed short circuit calculations for Panels OHNE1, WHNW1, and WHSW1 to allow the design to use more readily available lower rated KAIC panels. Performing and showing this calculation is a Tucson City requirement but is waived due to panel selections equal to Main Distribution Panel rating. 3. IE311 ONE LINE DIAGRAM: Should have included Panel OLNE1(Transformer TONE1) load on Panel OHNE1 panel load calculation. 4. IE411 ELECTRICAL SYMBOL, NOTES & DETAILS: Grounding wire for Telephone/Data Riser should be changed to a standard conductor size. Current size (#5 Cu) shown will be difficult to impossible to source. |
||
| 07/11/2025 | Commercial Mechanical | APPROVED | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Approved Reason: Date Completed : 7/10/2025 12:20:51 PM |
||
| 07/02/2025 | Site Engineering | APPROVED | |||
| 07/14/2025 | Water - PDSD | APPROVED | |||
| 07/16/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/11/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 7/10/2025 10:28:06 PM Plumbing Plan Revision Review: 1). General: Plan review request states Bldg 2, but the included plan set is for Bldg 3? Submit the correlating plan set -2018 IPC 106.3.1 |
||
| 07/15/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD ZONING REVIEW TRANSMITTAL FROM: Bobby Parsons Zoning Review Section PROJECT: TC-COM-0425-00796 4150 E. Los Reales Rd. Tucson, AZ 85756 Office – Build out of existing shell (2nd Review) TRANSMITTAL DATE: 7/15/2025 Resubmit a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the I-2 zone (UDC 4.7.30). Administrative and Professional Office is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standard 4.9.13.Q. 1. Comment: The plans submitted are for Building 3 not Building 2. Please submit the correct set of plans for the proposed work at Building 2. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 07/16/2025 | Fire New Construction | REVIEW COMPLETED | Incorrect Set of Plans uploaded on this resubmittal - Please require resubmit. | ||
| 07/01/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |