Permit Number: TC-COM-0425-00796
Parcel: 14044004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00796
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2025 Commercial Building APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 7/5/2025 6:12:42 PM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 7/9/2025 10:02:41 AM
07/11/2025 Commercial Electrical APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/3/2025 10:42:01 AM
1. IE113 ENLARGED OFFICE HVAC PLAN: Should have provided circuit information for bathroom power.
2. IE311: Should have performed short circuit calculations for Panels OHNE1, WHNW1, and WHSW1 to allow the design
to use more readily available lower rated KAIC panels. Performing and showing this calculation is a Tucson City
requirement but is waived due to panel selections equal to Main Distribution Panel rating.
3. IE311 ONE LINE DIAGRAM: Should have included Panel OLNE1(Transformer TONE1) load on Panel OHNE1 panel
load calculation.
4. IE411 ELECTRICAL SYMBOL, NOTES & DETAILS: Grounding wire for Telephone/Data Riser should be changed to
a standard conductor size. Current size (#5 Cu) shown will be difficult to impossible to source.
07/11/2025 Commercial Mechanical APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 7/10/2025 12:20:51 PM
07/02/2025 Site Engineering APPROVED
07/14/2025 Water - PDSD APPROVED
07/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/11/2025 Commercial Plumbing REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 7/10/2025 10:28:06 PM
Plumbing Plan Revision Review:
1). General: Plan review request states Bldg 2, but the included plan set is for Bldg 3? Submit the correlating plan set -2018
IPC 106.3.1
07/15/2025 Site Zoning REQUIRES RESUBMIT PDSD ZONING REVIEW TRANSMITTAL

FROM:
Bobby Parsons
Zoning Review Section

PROJECT:
TC-COM-0425-00796
4150 E. Los Reales Rd. Tucson, AZ 85756
Office – Build out of existing shell (2nd Review)

TRANSMITTAL DATE: 7/15/2025

Resubmit a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-2 zone (UDC 4.7.30). Administrative and Professional Office is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standard 4.9.13.Q.

1. Comment: The plans submitted are for Building 3 not Building 2. Please submit the correct set of plans for the proposed work at Building 2.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
07/16/2025 Fire New Construction REVIEW COMPLETED Incorrect Set of Plans uploaded on this resubmittal - Please require resubmit.
07/01/2025 PDSD Application Completeness Express REVIEW COMPLETED