Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0424-00707
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/06/2024 | Commercial Electrical | NOT REQUIRED | |||
05/06/2024 | Commercial Plumbing | NOT REQUIRED | |||
05/06/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/06/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show the location of the termination of the tank vent. Reference: Section1305.7, IMC 2018. 2. How will the maximum safe fill level of the inside tank be indicated at the fill location. Reference: Section 1306.4, IMC 2018. |
||
04/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |