Permit Number: TC-COM-0424-00699
Parcel: 130055920

Address:
2585 E 36TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0424-00699
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/17/2024 External Reviewers - Stantec REQUIRES RESUBMIT June 13, 2024
2nd Review

Seaver Franks Architects
Attn: Rick Huch/ Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: BOYS AND GIRLS CLUB
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0424-00699
Stantec Project Number: 185215066
Stantec File Number: TUC-24-040

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
E III-B 17,169 399 Yes Yes
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system and fire alarm
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. Addressed.

3. The plan-set indicates the installation of new mechanical units on the roof ranging from 450lbs – 850lbs. These units appear to be in different areas of the roof than the original units. Please provide an engineering analysis that indicates the proposed units can be placed at the locations indicated without additional reinforcement. Additionally, the proposed type 1 hood indicates a hanging weight of 559lbs. Please provide a structural analysis that the existing roof can support the hood and a design to accompany. [Ref. IBC 2018 Sec. 1604.4] Still Required: The structural plans do not include a design for a method of attachment of the hanger rods to the roof joists. {This comment is also included in the ‘Structural Comments’ section.}

4. Addressed.

5. New Comment: Note on the cover of the drawings that special inspection is required for field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A5.0

1. Addressed.

2. Addressed.

STRUCTURAL COMMENTS

General

1. The plan-set indicates the installation of new mechanical units on the roof ranging from 450lbs – 850lb. these units appear to be in different areas of the roof than the original units. Please provide an engineering analysis that the proposed units can be placed at the locations indicated without additional reinforcement. Additionally, the proposed type 1 hood indicates a hanging weight of 559lbs. Please provide a structural analysis that the existing roof can support the hood. [Ref. IBC 2018 Sec. 1604.4] Still Required: The structural plans do not include a design for a method of attachment of the hanger rods to the roof joists.

MECHANICAL COMMENTS

Sheet M2.0

1. Addressed.

PLUMBING COMMENTS

Sheet P1.0

1. Addressed.

2. New Comment: The new floor sink to the left of the booster pump in the pump room does not indicate a connection to the sewer. This floor sink also does not include a fixture mark. Please revise.

Sheet P1.1

1. New Comment: The plans do not indicate a gas connection to the gas water heater. Please revise.

Sheet P2.0

1. Addressed.

ELECTRICAL COMMENTS

1. There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com