Permit Number: TC-COM-0424-00699
Parcel: 130055920

Address:
2585 E 36TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0424-00699
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2024 Site Zoning APPROVED
05/14/2024 Site Engineering NOT REQUIRED
05/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/09/2024 External Reviewers - Stantec REQUIRES RESUBMIT May 3, 2024
1st Review

Seaver Franks Architects
Attn: Rick Huch/ Nurlan Herburger
2552 N. Alvernon Way
Tucson, Arizona 85712

Re: BOYS AND GIRLS CLUB
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0424-00699
Stantec Project Number: 185215066
Stantec File Number: TUC-24-040

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
E III-B 17,169 399 Yes Yes
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system and fire alarm
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], fire alarm system [2018 IBC Sec. 907], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

3. The plan-set indicates the installation of new mechanical units on the roof ranging from 450lbs – 850lbs. These units appear to be in different areas of the roof than the original units. Please provide an engineering analysis that indicates the proposed units can be placed at the locations indicated without additional reinforcement. Additionally, the proposed type 1 hood indicates a hanging weight of 559lbs. Please provide a structural analysis that the existing roof can support the hood and a design to accompany. [Ref. IBC 2018 Sec. 1604.4] {This comment is also included in the ‘Structural Comments’ section.}

4. The plan-set contains conflicting information. Detail 8 of sheet M2.0 of the mechanical plans indicates a fire-rated shaft per the architectural design for the kitchen hood exhaust, but the architectural plan does not contain details for the fire-rated shaft. Please coordinate and clarify.

Sheet A5.0

1. Please indicate a minimum of 5% but not less than one of the dining surfaces for the seating and standing spaces in the dining area as being accessible. [Ref. IBC 2018 Sec. 1108.2.9.1]

2. Please indicate the required 5’ diameter turning space in the unisex bathrooms. [Ref. ICC ANSI A117-2009 Sec. 603.2.1]

STRUCTURAL COMMENTS

General

1. The plan-set indicates the installation of new mechanical units on the roof ranging from 450lbs – 850lb. these units appear to be in different areas of the roof than the original units. Please provide an engineering analysis that the proposed units can be placed at the locations indicated without additional reinforcement. Additionally, the proposed type 1 hood indicates a hanging weight of 559lbs. Please provide a structural analysis that the existing roof can support the hood. [Ref. IBC 2018 Sec. 1604.4]

MECHANICAL COMMENTS

Sheet M2.0

1. Please provide a grease duct detail between the exhaust fan and the type 1 hood indicating compliance with the provisions of Section 506.3 of the 2018 International Mechanical Code.

PLUMBING COMMENTS

Sheet P1.0

1. Please provide grease interceptor sizing calculations in accordance with Section 1003.3 of the International Plumbing Code as amended by the City of Tucson.

Sheet P2.0

1. Please indicate a low-pressure cutoff installed on the proposed booster pump. [Ref. IPC 2018 Sec. 606.5.5]

ELECTRICAL COMMENTS

1. There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/14/2024 Fire New Construction REVIEW COMPLETED
04/19/2024 PDSD Application Completeness Express REVIEW COMPLETED