Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0424-00661
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2024 | Commercial Building | APPROVED | |||
05/01/2024 | Commercial Mechanical | APPROVED | |||
05/01/2024 | Commercial Plumbing | APPROVED | |||
04/30/2024 | Site Zoning | APPROVED | |||
05/01/2024 | Water - PDSD | APPROVED | |||
05/03/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/01/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide lighting controls as required the 2018 IECC section C405.2.1.3. 2 Indicate panel designation for all branch circuits. 3 Show the location of the breaker panel(s) associated with this project. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
04/22/2024 | Fire New Construction | REVIEW COMPLETED | |||
04/17/2024 | PDSD Application Completeness | REVIEW COMPLETED |