Permit Number: TC-COM-0325-00539
Parcel: 14042025A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0325-00539
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2025 Water - PDSD Standard APPROVED
05/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/24/2025 9:49:16 AM
1. General: The drawings provided at resubmittal are the incorrect drawings. It appears to be for another project. Provide
the correct drawings for this project.


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/24/2025 9:48:50 AM
1. General: The drawings provided at resubmittal are the incorrect drawings. It appears to be for another project. Provide
the correct drawings for this project.
04/24/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/24/2025 9:48:59 AM
1. General: The drawings provided at resubmittal are the incorrect drawings. It appears to be for another project. Provide
the correct drawings for this project.
04/24/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 4/24/2025 9:49:07 AM
1. General: The drawings provided at resubmittal are the incorrect drawings. It appears to be for another project. Provide
the correct drawings for this project.
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED