Permit Number: TC-COM-0226-00261
Parcel: 140410070

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0226-00261
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2026 Commercial Building Standard APPROVED
10/14/2026 Commercial Electrical Standard APPROVED Approved with comments added to plans:
Coordinate the placement of the Electrical Service Entrance and the access/egress door location, with the architectural drawings to ensure that the minimum distance of the door from the SES is met. NEC 110.26(C)(2)(b) Extra Working Space. Where the depth of the working space is twice that required by 110.26(A)(1), a single entrance shall be permitted. It shall be located such that the distance from the equipment to the nearest edge of the entrance is not less than the minimum clear distance specified in Table 110.26(A)(1) for equipment operating at that voltage and in that condition.
10/19/2026 Commercial Mechanical Standard APPROVED
10/19/2026 Commercial Plumbing Standard APPROVED
10/14/2026 Outdoor Lighting Standard APPROVED
10/19/2026 Water - PDSD Standard APPROVED
10/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/28/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review, contact CDRC@tucsonaz.gov
Incomplete project address on plans, direction (E for East) is missing. Please add complete project address to plans and resubmit.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
10/13/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0226-00261 (1st Review)
Project: Proposed construction of a 162,240 sf SHELL ONLY/Speculative Building and associated site work
Location: 3430 E VALENCIA RD
Review Date: 10/13/2026
Reviewer: John Mounsey – Engineering Associate
Reviewer Contact Information: john.mounsey@tucsonaz.gov

Site Engineering Comments:
1. Site Engineering has completed its review of the submitted plan set and cross-referenced it against the associated development package. However, Site Engineering is unable to grant final approval for Commercial Permit: TC-COM-0226-00261 until the associated revision to Development Package TD-DEV-1225-00310 has received full approval and has been issued. Please resubmit for final approval once the development package has been approved and issued by all applicable reviewers. For final approval - Ensure that all building plans match what is shown in the development package plan set.
10/19/2026 Site Zoning Standard REQUIRES RESUBMIT Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-1225-00310, and although the plans appear to be in compliance, Zoning cannot approve the building plan until the DP is approved by all review agencies.

For Site Zoning questions, please reach out to Krista at Krista.hansen@tucsonaz.gov.
10/19/2026 Fire New Construction Standard REVIEW COMPLETED
09/28/2026 PDSD Application Completeness Express REVIEW COMPLETED