Permit Number: TC-COM-0226-00261
Parcel: 140410070

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0226-00261
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2026 Restamp Commercial Building APPROVED
05/27/2026 Restamp Commercial Mechanical APPROVED
05/27/2026 Restamp Commercial Plumbing APPROVED
05/27/2026 Restamp Water - PDSD APPROVED
05/22/2026 Site Engineering Standard APPROVED
05/22/2026 Site Zoning Standard APPROVED Associated DP (TD-DEV-1225-00310) has been approved.
05/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/27/2026 Restamp Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00261 (3430 E VALENCIA RD TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. The provided electrical plan-set is marked as ‘Preliminary, Not for Construction’. Please provide the complete electrical plans as Sealed, signed and dated by the EEOR.
3. The provided plans are missing the outdoor lighting calculations and these calculations must be returned and corrected prior to electrical or outdoor lighting reviews can be approved.
05/27/2026 Restamp Outdoor Lighting REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0226-00261 (3430 E VALENCIA RD TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. The provided electrical plan-set is marked as ‘Preliminary, Not for Construction’. Please provide the complete electrical plans as Sealed, signed and dated by the EEOR.
3. The provided plans are missing the outdoor lighting calculations and these calculations must be returned and corrected prior to electrical or outdoor lighting reviews can be approved.
05/20/2026 PDSD Application Completeness Express REVIEW COMPLETED
05/27/2026 Restamp Fire New Construction REVIEW COMPLETED