Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0225-00339
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
N/A | Site Engineering Standard | PENDING ASSIGNMENT | |||
N/A | Site Zoning Standard | PENDING ASSIGNMENT | |||
N/A | Water - PDSD Standard | PENDING ASSIGNMENT | |||
03/08/2025 | Commercial Building Standard | REQUIRES RESUBMIT | March 4, 2025 1st Review Light+Path Architects LLC. Attn: Brian G. Hagedon 475 S. Gollob Road Tucson, Arizona 85710 Re: TEEN CHALLENGE BUILDING 2 – STAFF LIVING CORE, SHELL, & FITOUT City of Tucson Permit Number: TC-COM-0225-00339 Stantec Project Number: 185215066 Stantec File Number: TUC-25-026 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms R-2 V-B 16,332 78 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Water resistive barrier coating. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Note on the cover of the drawings that special inspection is required for water-resistive barrier coating [Ref. IBC 2018 Sec. 1705.16.1]. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Provide approved and listed through and membrane penetration assemblies and details. [Ref. IBC Sec. 708.7] Sheet GA111 1. Please provide fixture calculations for the proposed structure. [Ref. IBC 2018 Sec. 2902.1.1] Sheet A111 1. Please indicate Ext. Hall East (101) as a minimum 30min. fire rated corridor and the listed assembly to be used to achieve required fire-resistance. [Ref. IBC 2018 Sec. 1020.1] 2. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 3. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] Sheet A112 1. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 2. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M101 1. Please provide details indicating compliance with penetrations into the fire-rated wall assembly at the laundry room. Please also indicate compliance with Section 504.2 of the 2018 International Mechanical Code by indicating galvanized steel or aluminum and required thickness. Please also be sure to include details of the listed assembly allowing the duct to be ran within the wall and preserving rating. PLUMBING COMMENTS General 1. Sheet P200 is missing from the plan-set. Please provide. 2. Please provide isometric drawings for the plumbing systems. [Ref. IPC 2018 106.3.1] Sheet 202 1. Please identify the table used for the medium pressure gas pipe sizing. [Ref. IFGC 2018 Sec. 402.3] ELECTRICAL COMMENTS Sheet E511 1. Please provide the withstand rating (KAIC) for the fully rated CT Can. [Ref. NEC 2017 Art. 110.9] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
03/08/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | March 4, 2025 1st Review Light+Path Architects LLC. Attn: Brian G. Hagedon 475 S. Gollob Road Tucson, Arizona 85710 Re: TEEN CHALLENGE BUILDING 2 – STAFF LIVING CORE, SHELL, & FITOUT City of Tucson Permit Number: TC-COM-0225-00339 Stantec Project Number: 185215066 Stantec File Number: TUC-25-026 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms R-2 V-B 16,332 78 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Water resistive barrier coating. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Note on the cover of the drawings that special inspection is required for water-resistive barrier coating [Ref. IBC 2018 Sec. 1705.16.1]. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Provide approved and listed through and membrane penetration assemblies and details. [Ref. IBC Sec. 708.7] Sheet GA111 1. Please provide fixture calculations for the proposed structure. [Ref. IBC 2018 Sec. 2902.1.1] Sheet A111 1. Please indicate Ext. Hall East (101) as a minimum 30min. fire rated corridor and the listed assembly to be used to achieve required fire-resistance. [Ref. IBC 2018 Sec. 1020.1] 2. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 3. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] Sheet A112 1. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 2. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M101 1. Please provide details indicating compliance with penetrations into the fire-rated wall assembly at the laundry room. Please also indicate compliance with Section 504.2 of the 2018 International Mechanical Code by indicating galvanized steel or aluminum and required thickness. Please also be sure to include details of the listed assembly allowing the duct to be ran within the wall and preserving rating. PLUMBING COMMENTS General 1. Sheet P200 is missing from the plan-set. Please provide. 2. Please provide isometric drawings for the plumbing systems. [Ref. IPC 2018 106.3.1] Sheet 202 1. Please identify the table used for the medium pressure gas pipe sizing. [Ref. IFGC 2018 Sec. 402.3] ELECTRICAL COMMENTS Sheet E511 1. Please provide the withstand rating (KAIC) for the fully rated CT Can. [Ref. NEC 2017 Art. 110.9] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
03/08/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | March 4, 2025 1st Review Light+Path Architects LLC. Attn: Brian G. Hagedon 475 S. Gollob Road Tucson, Arizona 85710 Re: TEEN CHALLENGE BUILDING 2 – STAFF LIVING CORE, SHELL, & FITOUT City of Tucson Permit Number: TC-COM-0225-00339 Stantec Project Number: 185215066 Stantec File Number: TUC-25-026 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms R-2 V-B 16,332 78 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Water resistive barrier coating. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Note on the cover of the drawings that special inspection is required for water-resistive barrier coating [Ref. IBC 2018 Sec. 1705.16.1]. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Provide approved and listed through and membrane penetration assemblies and details. [Ref. IBC Sec. 708.7] Sheet GA111 1. Please provide fixture calculations for the proposed structure. [Ref. IBC 2018 Sec. 2902.1.1] Sheet A111 1. Please indicate Ext. Hall East (101) as a minimum 30min. fire rated corridor and the listed assembly to be used to achieve required fire-resistance. [Ref. IBC 2018 Sec. 1020.1] 2. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 3. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] Sheet A112 1. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 2. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M101 1. Please provide details indicating compliance with penetrations into the fire-rated wall assembly at the laundry room. Please also indicate compliance with Section 504.2 of the 2018 International Mechanical Code by indicating galvanized steel or aluminum and required thickness. Please also be sure to include details of the listed assembly allowing the duct to be ran within the wall and preserving rating. PLUMBING COMMENTS General 1. Sheet P200 is missing from the plan-set. Please provide. 2. Please provide isometric drawings for the plumbing systems. [Ref. IPC 2018 106.3.1] Sheet 202 1. Please identify the table used for the medium pressure gas pipe sizing. [Ref. IFGC 2018 Sec. 402.3] ELECTRICAL COMMENTS Sheet E511 1. Please provide the withstand rating (KAIC) for the fully rated CT Can. [Ref. NEC 2017 Art. 110.9] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
03/08/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | March 4, 2025 1st Review Light+Path Architects LLC. Attn: Brian G. Hagedon 475 S. Gollob Road Tucson, Arizona 85710 Re: TEEN CHALLENGE BUILDING 2 – STAFF LIVING CORE, SHELL, & FITOUT City of Tucson Permit Number: TC-COM-0225-00339 Stantec Project Number: 185215066 Stantec File Number: TUC-25-026 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms R-2 V-B 16,332 78 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Water resistive barrier coating. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Note on the cover of the drawings that special inspection is required for water-resistive barrier coating [Ref. IBC 2018 Sec. 1705.16.1]. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Provide approved and listed through and membrane penetration assemblies and details. [Ref. IBC Sec. 708.7] Sheet GA111 1. Please provide fixture calculations for the proposed structure. [Ref. IBC 2018 Sec. 2902.1.1] Sheet A111 1. Please indicate Ext. Hall East (101) as a minimum 30min. fire rated corridor and the listed assembly to be used to achieve required fire-resistance. [Ref. IBC 2018 Sec. 1020.1] 2. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 3. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] Sheet A112 1. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 2. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M101 1. Please provide details indicating compliance with penetrations into the fire-rated wall assembly at the laundry room. Please also indicate compliance with Section 504.2 of the 2018 International Mechanical Code by indicating galvanized steel or aluminum and required thickness. Please also be sure to include details of the listed assembly allowing the duct to be ran within the wall and preserving rating. PLUMBING COMMENTS General 1. Sheet P200 is missing from the plan-set. Please provide. 2. Please provide isometric drawings for the plumbing systems. [Ref. IPC 2018 106.3.1] Sheet 202 1. Please identify the table used for the medium pressure gas pipe sizing. [Ref. IFGC 2018 Sec. 402.3] ELECTRICAL COMMENTS Sheet E511 1. Please provide the withstand rating (KAIC) for the fully rated CT Can. [Ref. NEC 2017 Art. 110.9] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
03/08/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | March 4, 2025 1st Review Light+Path Architects LLC. Attn: Brian G. Hagedon 475 S. Gollob Road Tucson, Arizona 85710 Re: TEEN CHALLENGE BUILDING 2 – STAFF LIVING CORE, SHELL, & FITOUT City of Tucson Permit Number: TC-COM-0225-00339 Stantec Project Number: 185215066 Stantec File Number: TUC-25-026 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms R-2 V-B 16,332 78 Yes Yes Separate Permits: Automatic fire sprinklers and fire alarm. Deferred Submittals: None. Special Inspections: Water resistive barrier coating. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Note on the cover of the drawings that special inspection is required for water-resistive barrier coating [Ref. IBC 2018 Sec. 1705.16.1]. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. 3. Provide approved and listed through and membrane penetration assemblies and details. [Ref. IBC Sec. 708.7] Sheet GA111 1. Please provide fixture calculations for the proposed structure. [Ref. IBC 2018 Sec. 2902.1.1] Sheet A111 1. Please indicate Ext. Hall East (101) as a minimum 30min. fire rated corridor and the listed assembly to be used to achieve required fire-resistance. [Ref. IBC 2018 Sec. 1020.1] 2. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 3. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] Sheet A112 1. The 1-hr. rated assembly using ESR-1748 indicated at Ext. Hall West (102) does not meet the listed assembly criteria on the evaluation report of a minimum 10’ separation distance from adjacent construction. Please revise. [Ref. ICC ESR-1748 Sec. 4.6] 2. Please indicate door “011” with a minimum fire resistance rating of 20 minutes. [Re. IBC 2018 Sec. 716.1(2)] STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS Sheet M101 1. Please provide details indicating compliance with penetrations into the fire-rated wall assembly at the laundry room. Please also indicate compliance with Section 504.2 of the 2018 International Mechanical Code by indicating galvanized steel or aluminum and required thickness. Please also be sure to include details of the listed assembly allowing the duct to be ran within the wall and preserving rating. PLUMBING COMMENTS General 1. Sheet P200 is missing from the plan-set. Please provide. 2. Please provide isometric drawings for the plumbing systems. [Ref. IPC 2018 106.3.1] Sheet 202 1. Please identify the table used for the medium pressure gas pipe sizing. [Ref. IFGC 2018 Sec. 402.3] ELECTRICAL COMMENTS Sheet E511 1. Please provide the withstand rating (KAIC) for the fully rated CT Can. [Ref. NEC 2017 Art. 110.9] Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
03/04/2025 | Fire New Construction Standard | REVIEW COMPLETED | Project shall comply with the 2018 IFC chapter 906 Portable Fire Extinguishers | ||
02/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |