Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0224-00317
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2024 | Site Zoning | APPROVED | |||
| 03/19/2024 | Water - PDSD | APPROVED | |||
| 03/19/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 03/04/2024 | Fire New Construction | NOT REQUIRED | |||
| 03/08/2024 | Site Engineering | NOT REQUIRED | |||
| 03/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/13/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Please amend plans to indicate the location of the new light pole as shown on sheet E1. IBC 107.2.1 2. Further, related to above comment, please provide structural calculations for the new light pole and foundation IBC 107.2.7 Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994 |
||
| 03/13/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response 1 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. Ref; 2012 City of Tucson Outdoor Lighting Code. |
||
| 03/19/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide a cleanout at the junction of the building drain and the building sewer. Reference: Section 708.1.3, IPC 2018. | ||
| 02/28/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |