Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0223-00676
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/02/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Ref; Power Plan Line Diagram. 1 Provide complete details, structural, footings, height, etc. for the poles being utilized for installing the overhead Quadraplex cable. 2 Type XLPE Quadraplex cable is normally used by utility companies and therefore is not recognized or identified per the NEC. Provide complete manufacturer cut sheets showing details of construction materials and all information, and or markings, amp ratings, printed on the cables as required per NEC art 310.120. Include recommended installation instructions per the manufacturer. NEC 110.3. 3 Provide a grounding detail for the transformers. 4 Indicate conduit, conductor sizes and types, quantities, for the Electrical Service Secondary Conductors. Ref; 2018 IBC section 108.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
04/12/2023 | PDSD Application Completeness | REVIEW COMPLETED |