Permit Number: TC-COM-0125-00169
Parcel: 14041124E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0125-00169
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2025 12:12:24 PM



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 2/17/2025 3:52:26 PM
02/17/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2025 1:45:27 PM
02/17/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 2/17/2025 3:09:43 PM
First Plumbing Review: OK
02/18/2025 Site Zoning Standard APPROVED
02/24/2025 Water - PDSD Standard APPROVED
02/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/17/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 2/4/2025 12:32:18 PM
1. E0.0: Where is Rack B and GC-B located and circuited from (shown in Refrigeration Equipment Schedule). Could not
locate anywhere else in the electrical design.
2. E1.0C: Lighting Note: Calls out to refer to sheet E0.1 for mounting heights but this information is not on sheet E0.1 but
on sheet E0.0. Comment applies to sheet E1.0D too. Correct or coordinate.
3. E1.0D: Need to provide an interior lighting Comcheck to show lighting design is IECC compliant. Suggest to place
comcheck cover sheet on either E1.0C or E1.0D (full report is not required).
4. E1.2D: could not locate Key Notes 2 and 9.
5. E1.2D: Should show wp/GFI receptacle near ‘New Grocery Generator’.
6. E4.0: The circuit breakers to xfmr TLF1 (112.5 KVA) and TFL2 (45 KVA) in panel HF are not properly sized. The 350-
amp and 250-amp circuit breakers do not protect the xfmr feeders and xfmr TFL2 is not in compliance with NEC table
450.3(B). Comment only, suggest using protection shown in the feeder schedule.
7. E4.0: Comment only, suggest moving Refrigeration Equipment Schedule to this sheet vs current sheet E0.0.
02/17/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 2/4/2025 12:32:18 PM
1. E0.0: Where is Rack B and GC-B located and circuited from (shown in Refrigeration Equipment Schedule). Could not
locate anywhere else in the electrical design.
2. E1.0C: Lighting Note: Calls out to refer to sheet E0.1 for mounting heights but this information is not on sheet E0.1 but
on sheet E0.0. Comment applies to sheet E1.0D too. Correct or coordinate.
3. E1.0D: Need to provide an interior lighting Comcheck to show lighting design is IECC compliant. Suggest to place
comcheck cover sheet on either E1.0C or E1.0D (full report is not required).
4. E1.2D: could not locate Key Notes 2 and 9.
5. E1.2D: Should show wp/GFI receptacle near ‘New Grocery Generator’.
6. E4.0: The circuit breakers to xfmr TLF1 (112.5 KVA) and TFL2 (45 KVA) in panel HF are not properly sized. The 350-
amp and 250-amp circuit breakers do not protect the xfmr feeders and xfmr TFL2 is not in compliance with NEC table
450.3(B). Comment only, suggest using protection shown in the feeder schedule.
7. E4.0: Comment only, suggest moving Refrigeration Equipment Schedule to this sheet vs current sheet E0.0.
02/05/2025 Fire New Construction Standard REVIEW COMPLETED Fire alarm and fire sprinklers submittal s shall comply with the following codes and standards:
2024 International Fire Code
2022 Edition of NFPA 72
2022 Edition of NFPA 13
01/31/2025 PDSD Application Completeness Express REVIEW COMPLETED
02/24/2025 Site Engineering Standard REVIEW COMPLETED