Permit Number: T22CM05804
Parcel: 14042025A

Address:
2717 E CORONA RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM05804
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 11/5/2024 12:22:47 AM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/4/2024 11:59:16 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/4/2024 10:05:03 AM
Shell Build only. Tenant buildouts (offices) will require additional Permitting and Plan review.




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 10/30/2024 3:48:13 PM





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 11/3/2024 9:37:58 PM
First Revised Plumbing Review: OK
11/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2024 Site Engineering REQUIRES RESUBMIT 1. The building area shown on these building plans (146,963sf) does not match what is shown on the approved development package DP22-0214 (146,804sf). The plans must match to be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
11/21/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05804 – DP22-0214
2713 E Corona Rd – I-1
New Warehouse Building – (1st Revision, 1st Review)

TRANSMITTAL: November 21, 2024

This site is located in I-1 Zone (UDC Article 4.7.29).

1. Zoning has reviewed the revision to the building plans for compliance with development package (DP) DP22-0214 and although the plans appear to match until the DP revision has been approved by all review agencies Zoning cannot approve the building plans.

2. The DP sheets provided in the building plan either need to be the stamped approved plans, or marked for reference only. If you elect to mark the DP for reference only do not mark the Utility sheets for reference only as Plumbing needs to review.

The following DP comments effect several sheets within this building plan and will need to be addressed

1. COMMENT: 2-06.4.9.H.5.a – The wheel stop location dimension shown on detail 9 sheet G3.0 is not correct. Review UDC Article 7.4.6.H.3 and provide the correct dimension.

2. COMMENT: 2-06.4.9.H.5.d – As you are proposing short-term bicycle parking on site the short-term bicycle parking calculation shall state the number required and provided.

3. COMMENT: 2-06.4.9.H.5.d – Detail 5 sheet G3.1 demonstrate how the requirements of UDC Article 7.4.9.B.1.e 7.4.9.B.2.f & .g. are met.

4. COMMENT: 2-06.4.9.H.5.d – Detail 5 sheet G3.1 shows a dimension form the middle of the rack to edge of sidewalk and states that “EACH BIKE IS REQUIRED TO HAVE 2’ x 6’ (+/-) CLEARANCE AREA”. If the distance from middle of rack is only 2’ to edge of the sidewalk there is no way the required 2’ x 6” requirement is met, UDC Article 7.4.9.F.2.f and figure 7.4.9-C.
5. COMMENT: 2-06.4.9.R – Provide sidewalk width dimensions for the sidewalks shown on the plan.


If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/25/2024 Water - PDSD REQUIRES RESUBMIT The Site Utility Plan, C2.0, shows a 1-1/2” water meter, a 2” reduced pressure backflow prevention assembly, and a 2” domestic water service to the building. The plumbing plans, P1.0, P2.4, and P4.1, show a 3” water service pipe entering the building. The domestic water calculations on plumbing drawing, P6.1, also calls for a 2” water meter. Coordinate the civil and plumbing drawings. Reference: Section 107.2.1, IBC 2018.
11/07/2024 Fire New Construction REVIEW COMPLETED
10/29/2024 PDSD Application Completeness Express REVIEW COMPLETED