Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2023 Commercial Plumbing APPROVED Water review
01/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM05804

GENERAL:


Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
APPROVED


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
Approved/Subject to field approval for Shell and Core only


ELECTRICAL REVIEW COMMENTS
APPROVED


PLUMBING REVIEW COMMENTS:
DENIED
Second Plumbing Review:
1).thru 3 OK
4). The calculations for the roof drain square footage to GPM loads are incorrect on plan pages P2.2, P2.3, P2.4. The GPM loads currently shown are the maximum GPM loads given in the 1/4" per foot column in -IPC Table 1106.2
5). Same- Plan page P4.1 Sprinkler system stub in needs a backflow preventer. IPC 608.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/13/2022 Site Engineering REQUIRES RESUBMIT Combo permits cannot be approved until their associated development package has been approved. This permit will be reviewed when DP22-0214 is reviewed.

Lianne Evans
lianne.evans@tucsonaz.gov
520-837-5341
12/01/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANS



FROM: PDSD Zoning Review



PROJECT: T22CM05804 – DP22-0214

2713 E Corona Rd – I-1

New Warehouse Building – (2nd Review)



TRANSMITTAL: December 01, 2022



COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



This site is located in I-1 Zone (UDC Article 4.7.29).



Zoning has reviewed the building plans for compliance with DP22-0214, and although the plans appear to be in compliance, until the DP is approved by all review agencies Zoning cannot approve the building plans.



The development package sheets provided in the building plan set shall either be the stamped approved DP sheets, marked for reference only or removed from the building plan set. If you elect to mark the plans for reference only or remove the DP sheets from the plan ensure that the Utility plans are not marked for reference or removed.



If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/28/2022 Fire New Construction REVIEW COMPLETED
11/30/2022 PDSD Application Completeness Express REVIEW COMPLETED