Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T22CM04922
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/29/2022 | External Reviewers - SAFEBuilt | APPROVED | Activity Number: T22CM04922 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Conditionally Approved 1. Sheet A0.01: The trash discharge room construction is required to have a fire resistance rating not less than the required fire rating of the shaft enclosure. Additionally, the doors are required to meet the rating of the shaft enclosure. Provide a correctly rated trash discharge room in accordance with Section 713.13.4. NOT COMPLIED. NOTE: The trash room door is not properly rated. Rate the door in accordance with SECTION 713.13.4 as stated numerous times in previous reviews. MECHANICAL REVIEW COMMENTS: Conditionally Approved 3. Provide fire damper where duct penetrates the horizontal fire assembly sheet m2.01b (IMC2018,607.6.1) the 40 by 40 duct going down to lower level area b from level 1 area b needs a fire damper Complied Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Conditionally Approved Third Plumbing Review: Ok Subject to Field inspections 1). -Roof area Floor sink on plan page P2.14B can't receive storm water- IPC 1101.3 ** added 6" curb will not prevent roof top floor sink from receiving rain water, suggest install over hang or locate floor sink in building** IF FLOOR SINK COVER IS TO BE INSTALLED AS STATED ON P2.14B, IT WILL NEED TO BE INSTALLED WITH AN AIR GAP DEVICE SO SOFTNER DISCHAREG CAN FUNCTION** 2 thru 3 OK 4). OK 5 thru 7 OK 8). OK - add trap guard in floor sinks 9). OK Add trap guard in floor sinks. 10 thru 19 OK 20). OK-BBQ grill & Firepit enclosures need cross ventilation louvers. -IFGC 304, 305.1 **SUBJECT TO FIELD INSPECTIONS TO BE INSTALLED PER MANUFACTURER SPECS** 21).OK-Amenity Plan page A2.15 shows overhead construction above Gas BBQ grills, exhaust hood will be required. -IFGC 623.5, 305.1 ** suggest remove overhead construction above cooking surface** 22). Where is the corner deck drain for the corner deck on level 13 on plan page P2.13B, as shown on the same deck on level 12? -IPC 106.3.1 ** OK-SUBJECT TO FIELD INSPECTION, WATER CAN'T BUILD UP ON DECK & CAUSE DAMAGE TO BLDG.** If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
01/09/2023 | Site Engineering | APPROVED | restamp required | ||
12/20/2022 | Site Zoning | APPROVED | |||
01/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/09/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The water calculations on sheet P0.03, CONS-3_Plan Set_v1.pdf, have been revised to call for two 3” water meters and a peak flow of 700 GPM. This new flow will require a 6” water meter. [Initial comment: The water calculations show that two 3” water meters are being manifolded to serve 592 GPM to the building. Tucson Water will not allow water meters to be manifolded to achieve additional capacity. Provide a 4” water meter which can serve 600 GPM.] | ||
12/20/2022 | Design Review | REVIEW COMPLETED | Design Professional Approval | ||
01/03/2023 | Fire New Construction | REVIEW COMPLETED | |||
12/06/2022 | PDSD Application Completeness | REVIEW COMPLETED |