Permit Number: T22CM03955
Parcel: 14044004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.2

Permit Number - T22CM03955
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2025 Site Zoning APPROVED
01/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/20/2024 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 12/20/2024 10:01:25 AM
1. Sheet E4.2: Per NEC 110..26(D) the panels in the warehouse space require lighting. Need to provide Sheet E4 that
shows lighting in/around the power panels inside the building. Not Addressed.