Permit Number: T22CM03954
Parcel: 14044004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM03954
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2023 Site Engineering APPROVED
06/12/2023 Site Zoning APPROVED
06/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM03954

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer (from previous submittal TUC7367001.101922)
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 10/31/2022 5:59:58 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


Building(B) Reviewer (from previous submittal TUC7367001.052522)
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/1/2022 7:05:09 PM


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 6/8/2023 8:10:11 PM
1. Provide mechanical plans (IMC2018,106.3.1) Not Complied
2. Provide ventilation calculations (IMC2018,,403.3.1.1.1) Not Complied
3. Provide a detailed narrative on the process that occurs in the warehouse (e.g. what materials are you storing in the warehouse, what type of forklifts are you using in the warehouse is it fuel or electric) (imc2018,106.3.1) Not Complied
All violations not complied


Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 6/9/2023 1:29:36 PM


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 6/10/2023 2:32:39 PM
Third Plumbing Review: OK
06/21/2023 Fire New Construction REVIEW COMPLETED
06/07/2023 PDSD Application Completeness Express REVIEW COMPLETED