Permit Number: T22CM03954
Parcel: 14044004C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM03954
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2024 Commercial Plumbing APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 11/28/2024 2:14:55 PM
12/23/2024 Commercial Structural APPROVED Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/25/2024 12:53:43 PM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/25/2024 12:53:36 PM
12/23/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/23/2024 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 11/21/2024 10:09:47 AM
1 E4.2 Per NEC 110..26(D) requires lighting for the power panels.
Comment only: Any 'Cold Dark Shell' should have stumble lighting. Should install some interior lighting to reach 1 lux (0.1
foot candle).
12/09/2024 Site Engineering REQUIRES RESUBMIT 1. The plans for this building permit show 158,944sf floor area, but the development package DP22-0122 approved 9/17/2024 shows 158,908sf floor area. The floor area must match. Either revise the floor area on the building plans or submit a revision to the development package.

Mike Ortiz
michael.ortiz@tucsonaz.gov
12/16/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM03954 – DP22-0122
4150 E Los Reales Rd – 1-2
Shell Building (2nd Revision, 1st Review)

TRANSMITTAL: December 16, 2024
This site is located in 1-2 Zone (UDC 4.7.30), Commercial Storage use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.10.A & 4.9.13.O.

Zoning has reviewed the building plans for compliance with DP22-0122 and the following comments need to be addressed.

1. The square footage for building 2, 158,944, does not match what is shown on the DP, 158,908. The square footages shall match.

2. There does not appear to be any access provided for the new rollup doors shown on the north and south elevations of the building. Clarify what is proposed.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
12/06/2024 Fire New Construction REVIEW COMPLETED
11/20/2024 PDSD Application Completeness Express REVIEW COMPLETED