Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T22CM03953
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2023 | Commercial Plumbing | APPROVED | |||
02/17/2023 | External Reviewers - SAFEBuilt | APPROVED | Activity Number: T22CM03953 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. BUILDING REVIEW COMMENTS: Conditionally Approved Sheet Cold dark shell (A0.1a) MECHANICAL REVIEW COMMENTS: Conditionally Approved Shell plans approved, will require mechanical plans when a tenant is provided cancel previous corrections ELECTRICAL REVIEW COMMENTS Conditionally Approved E4.2 EOR shall provide service receptacle by each 240/208/120V panel (such as Panel LHPA is shown in Southwest corner) as per NEC 210.64. This shall be incorporated by the EOR into their IFC set. If the EOR does not believe this is acceptable, they should resubmit their proposed design. The EOR should also provide 4-5 additional service receptacles around the interior perimeter of the building. PLUMBING REVIEW COMMENTS: Conditionally Approved Third Plumbing Review: =OK Subject to Field inspections 1).OK 2). Ok Subject to Field Inspections-Civil & plumbing Plan water main tie in locations still don't appear to correlate 3). OK 4). OK If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
02/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
02/22/2023 | Fire New Construction | REQUIRES RESUBMIT | Comments: You shall provide the following notes on sheet A0.1: Fire sprinkler underground plans shall be submitted to and a permit obtained from TFD Fire sprinkler plans shall be submitted to and a permit obtained from TFD Fire pump plans shall be submitted to and a permit obtained from TFD Fire alarm plans shall be submitted to and a permit obtained from TFD Building shall be tested for ERRC by PCWIN and the report provided to TFD prior to the TCO Owner shall provide KNOX key boxes and KNOX Locking F.D.C. caps Section 901.4.6 Pump and riser room size. Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation, as defined by the manufacturer, with sufficient working space around the stationary equipment. Clearances around equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair, or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly. Fire pump and automatic sprinkler system riser rooms shall be provided with doors and unobstructed passageways large enough to allow removal of the largest piece of equipment. Section 901.4.6.3 Environment. Automatic sprinkler systems riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40 degrees Fahrenheit. Heating units shall be permanently installed. Section 901.4.6.4 Lighting. Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms. Section 3206.7.5 Number of doors required. The required fire department access doors shall be distributed such that the lineal distance between adjacent fire department access doors does not exceed 125ft measured center to center. Fire department connection shall face the street side IFC 2018, Chapter 9, Section 912.2.1 Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
02/24/2023 | Site Engineering | REQUIRES RESUBMIT | See Zoning Comment | ||
02/22/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM03953 – DP22-0122 4150 E Los Reales Rd – 1-2 Shell Building (3rd Review) TRANSMITTAL: February 22, 2023 This site is located in 1-2 Zone (UDC 4.7.30), Commercial Storage use is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standard 4.9.10.A & 4.9.13.O. 1. Zoning has reviewed the building plans for compliance with DP22-0122 and although it appears that the building plans match the DP, the development package sheets provided in the building plans either need to be the approved stamped by PDSD CDRC, development pack sheets, marked for reference only or removed from the building plans. Zoning acknowledges that Safebuilt has stamped the DP sheets but this stamp does not approve the development package. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |