Permit Number: DP22-0032
Parcel: 141010130

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.3

Permit Number - DP22-0032
Review Name: DEVELOPMENT PACKAGE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2023 NPPO APPROVED
12/20/2022 Site Landscape APPROVED The NPPO tree quantities do not match the landscape legend quantities. Make sure to add 50 - 15 gallon Prosopis spp.
02/16/2023 CDRC Post Review PENDING ASSIGNMENT
01/23/2023 Commercial Plumbing REQUIRES RESUBMIT Lots 20 and 140 have a FFE that is more than 12” above the rim elevation of the next upstream manhole and lot 204 has a FFE that is 12” above the rim elevation of the next upstream manhole. These lots may not have a backwater valve. [Third comment: The FFE of each lot and the rim elevation of each manhole has been changed from the second submittal. Lots 14, 61, and 132 require backwater valves, lot 25, 48, and 204 may not have backwater valves. Note that Section 714.1, IPC 2018, as amended by the City of Tucson, states , “Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed…”, if, however, the finish floor elevation is 12 inches or more above the elevation of the next upstream manhole cover, no backwater valve shall be installed.] [Second comment: The FFE of each lot has been changed from the first submittal. The sewer layout, including points of connection to the proposed public sewers, proposed manhole rim and invert elevations must be shown to verify which lots require the installation of backwater valves.] [Initial comment: Revise the site drawings to indicate which lots will require backwater valves because the rim elevation of the next upstream sanitary manhole is less than 12” below the proposed first floor elevations. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.]
02/16/2023 External Reviewers - Pima County Addressing REQUIRES RESUBMIT Requires resubmit; See attached plans reviewed by; Nicholas Jordan Site Review Project Manager - Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-9623
01/04/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: La Escalera Residential, Lots 1-219
Development Package (5th Review)
DP21-0032

TRANSMITTAL DATE: January 04, 2023

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is February 20, 2023

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

1. Until this comment is addressed Zoning cannot approve the DP. COMMENT: 2-06.4.7.A.6.a – Provide a copy of the Design Review approval letter with the next submittal, see PAD-38 Part 5 A

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov