Permit: TC-RES-1123-09203
Permit Details
Status:
Inspections Complete
Type:
Residential Building - One or Two Family
Address:
4929 S CHERRY AV
Address NEW:
4929 S CHERRY AV
Apply Date:
11/01/2023
Applicant:
Daniel Simmons
Description:
CE-VIO0223-02016 Fire Damage Repair
Permit Reviews
Permit Number - TC-RES-1123-09203
Permit Status: Inspections complete
Permit Description: CE-VIO0223-02016 Fire Damage Repair
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/08/2023 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 12/14/2023 | APPROVED |
| 11/06/2023 | RESIDENTIAL NEW DWELLING v.1 | 11/28/2023 | APPROVED |
Outstanding Inspections
Permit Status: Inspections Complete
Permit Number: TC-RES-1123-09203
Permite Description: CE-VIO0223-02016 Fire Damage Repair
Total Outstanding Inspections - 6
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2024 | RSBU - Building Final | N/A | Re-inspection required | 7/11/24:House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. 7/12/24: House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 07/11/2024 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 7/11/24:House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 07/10/2024 | COT - RSEL - Electrical Final | N/A | Re-inspection required | 7/10/24: House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 07/10/2024 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 7/10/24: House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
| 02/22/2024 | COT - BULD - SWG Clearance | N/A | Not Ready | Not Ready - consult |
| 07/10/2024 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Re-inspection required | 7/10/24: House is at Final inspection without calling for intermediate inspections, letter is required from registered contractor/electrician/plumber/mechanical stating that all work completed meets or exceeds the requirements of the IRC. Liability will need to be taken by contractor, Arc-fault breaker's missing throughout, HVAC not hooked up, range plug is not made up, kitchen circuit not GFCI, receptacles in bedroom are not energized, water closet needs to be caulked, receptacle for dishwasher needs to be GFCI, sediment trap required at water heater. Water heater vent needs to properly terminate to exterior, combustion air requirements not met, door not allowed at laundry room, GFCI receptacle required at laundry room, water hammer arrestor required at laundry, fridge, dishwasher, T&P discharge must be to exterior of home, carbon monoxide sensor required, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |
Completed Inspections
Permit Status: Inspections Complete
Permit Number: TC-RES-1123-09203
Permit Description: CE-VIO0223-02016 Fire Damage Repair
Total Completed Inspections - 10
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2024 | COT - RSBU - Roof Nailing | Passed | 1/29/24: new 2x4 wall at bedroom needs to be properly fastened to slab, existing 2x8 rafters to remain missing H2.5 clips, missing double 2x8 below RTU, H2.5 missing at new 2x8 rafters, existing 2x6 roof rafters missing H2.5 at bearing points, missing H2.5 at new 2x6 rafters, braced wall on east wall not complete missing anchors bolts at bottom plate and 2x4 not properly fastened to sheathing or bottom plate, braced wall nail schedule is not per plan, new braced wall panels missing per plan. 1/31/24: corrections made |
|
| 01/31/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 1/29/24: new 2x4 wall at bedroom needs to be properly fastened to slab, existing 2x8 rafters to remain missing H2.5 clips, missing double 2x8 below RTU, H2.5 missing at new 2x8 rafters, existing 2x6 roof rafters missing H2.5 at bearing points, missing H2.5 at new 2x6 rafters, braced wall on east wall not complete missing anchors bolts at bottom plate and 2x4 not properly fastened to sheathing or bottom plate, braced wall nail schedule is not per plan, new braced wall panels missing per plan. 1/31/24: corrections made |
|
| 03/24/2025 | COT - RSPL - Gas Pressure Test | Passed | ||
| 03/27/2025 | BULD - Electrical Clearance | Passed | ||
| 03/27/2025 | RSBU - Building Final | Passed | ||
| 03/27/2025 | COT - RSPL - Plumbing Final | Passed | 27 March 25 All corrections have been made. |
|
| 03/27/2025 | COT - RSEL - Electrical Final | Passed | 27 March 25 All corrections have been made. |
|
| 03/27/2025 | COT - RSEL - Grounding/Bonding | Passed | ||
| 03/27/2025 | COT - RSME - Mechanical Final | Passed | ||
| 03/27/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed |