Permit: TC-RES-0825-03916
Permit Details
Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
5846 E GRANT RD
Address NEW:
5846 E GRANT RD
Apply Date:
08/07/2025
Applicant:
Brandon Filipp
Description:
REV1: installation of 125 AMP Electrical Service in the subject location, instead of the 200 AMP requested in the original set of Approved Construction Plans. Additionally, instead of an overhead electrical line drop, there is an existing underground feeder line which will be utilized (TEP is unable to provide an overhead line drop to the subject property) THE SCOPE OF WORK INVOLVES THE REMEDIATION OF FIRE DAMAGE AND RENOVATION OF AN EXISTING TOWNHOME. MAJOR RENOVATIONS INCLUDE: 1. FINISHES: REPLACE ALL INTERIOR FINISHES, REPLACE DRYWALL AT CEILINGS AND INTERIOR WALLS, FUR OUT THE INTERIOR SIDE OF EXTERIOR NON-FRAMED WALLS (I.E. BLOCK WALLS) AND INSTALL NEW DRYWALL, REPLACE DOORS AND WINDOWS, AND REPLACE INSULATION. 2. STRUCTURAL: ADDRESS FINDINGS OF THE SOUTHWEST ENGINEERING, STRUCTURAL ENGINEERS, LLC STRUCTURAL INSPECTION REPORT SWE JOB# 2533 (SUBMITTED ALONG WITH THESE PLANS), INCLUDING DEMOLITION AND REBUILT OF FIRE DAMAGED BACK PORCH AND STORAGE, REPLACEMENT OF SIX SEVERELY FIRE DAMAGED ROOF RAFTERS AND TWO OTHER ROOF RAFTERS FOUND TO BE CRACKED, REINFORCEMENT OF TEN ROOF RAFTERS WITH MINOR FIRE DAMAGE, AND DEMOLITION AND REPLACEMENT OF APPROX. 546 SF OF FIRE DAMAGED ROOF SHEATHING OVER SAID RAFTERS. ADDITIONALLY, EXTEND FIRE WALLS BETWEEN SUBJECT AND ADJACENT TOWNHOMES TO A HEIGHT NOT LESS THAN 30" ABOVE ROOF BY INSTALLING FIREWALL PARAPETS, INSPECT AND REPAIR/REPLACE ANY OTHER DAMAGED ROOF RAFTERS AND OTHER ROOF FRAMING MEMBERS (IF ANY ARE FOUND TO BE DAMAGED), INSPECT AND REPLACE ANY DAMAGED ROOF DECKING, AND CREATE AN OPENING FROM THE KITCHEN TO THE LIVING ROOM. 3. ELECTRICAL: REPLACE EXISTING ELECTRICAL PANEL, ELECTRICAL DISTRIBUTION AND FIXTURES. 4. PLUMBING: INSPECT SEWER LINE FROM WITHIN THE HOME TO THE HCS AND REPAIR/REPLACE AS NECESSARY IF ANY PORTIONS OF IT ARE FOUND DAMAGED, REPLACE EXISTING WATER DISTRIBUTION, REPLACE EXISTING PLUMBING FIXTURES, AND REPLACE EXISTING WATER HEATER. EXISTING WATER AND GAS METERS REMAIN. 5. MECHANICAL: REPLACE EXISTING HVAC WITH NEW HVAC SYSTEM, REPLACE EXISTING MECHANICAL DISTRIBUTION, AND REPLACE EXISTING EXHAUST FANS. 6. GENERAL: INSTALL A NEW FLAT ROOF ON HOME AND BACK PORCH, INSPECT ROOF OF FRONT PORCH AND GARAGE AND REPLACE AS MIGHT BE NECESSARY FROM THE RESULTS OF THE INSPECTION, REPAIR REAR FENCE ON WEST SIDE OF GARAGE AND REPAINT HOME EXTERIOR AS NECESSARY.
Permit Reviews
Permit Number - TC-RES-0825-03916
Permit Status: Inspections
Permit Description: REV1: installation of 125 AMP Electrical Service in the subject
location, instead of the 200 AMP requested in the original set of Approved Construction Plans.
Additionally, instead of an overhead electrical line drop, there is an existing underground feeder line
which will be utilized (TEP is unable to provide an overhead line drop to the subject property)
THE SCOPE OF WORK INVOLVES THE REMEDIATION OF FIRE DAMAGE AND RENOVATION OF AN EXISTING TOWNHOME. MAJOR RENOVATIONS INCLUDE:
1. FINISHES: REPLACE ALL INTERIOR FINISHES, REPLACE DRYWALL AT CEILINGS AND INTERIOR WALLS, FUR OUT THE INTERIOR SIDE OF EXTERIOR NON-FRAMED WALLS (I.E. BLOCK WALLS) AND INSTALL NEW DRYWALL, REPLACE DOORS AND WINDOWS, AND REPLACE INSULATION.
2. STRUCTURAL: ADDRESS FINDINGS OF THE SOUTHWEST ENGINEERING, STRUCTURAL ENGINEERS, LLC STRUCTURAL INSPECTION REPORT SWE JOB# 2533 (SUBMITTED ALONG WITH THESE PLANS), INCLUDING DEMOLITION AND REBUILT OF FIRE DAMAGED BACK PORCH AND STORAGE, REPLACEMENT OF SIX SEVERELY FIRE DAMAGED ROOF RAFTERS AND TWO OTHER ROOF RAFTERS FOUND TO BE CRACKED, REINFORCEMENT OF TEN ROOF RAFTERS WITH MINOR FIRE DAMAGE, AND DEMOLITION AND REPLACEMENT OF APPROX. 546 SF OF FIRE DAMAGED ROOF SHEATHING OVER SAID RAFTERS. ADDITIONALLY, EXTEND FIRE WALLS BETWEEN SUBJECT AND ADJACENT TOWNHOMES TO A HEIGHT NOT LESS THAN 30" ABOVE ROOF BY INSTALLING FIREWALL PARAPETS, INSPECT AND REPAIR/REPLACE ANY OTHER DAMAGED ROOF RAFTERS AND OTHER ROOF FRAMING MEMBERS (IF ANY ARE FOUND TO BE DAMAGED), INSPECT AND REPLACE ANY DAMAGED ROOF DECKING, AND CREATE AN OPENING FROM THE KITCHEN TO THE LIVING ROOM.
3. ELECTRICAL: REPLACE EXISTING ELECTRICAL PANEL, ELECTRICAL DISTRIBUTION AND FIXTURES.
4. PLUMBING: INSPECT SEWER LINE FROM WITHIN THE HOME TO THE HCS AND REPAIR/REPLACE AS NECESSARY IF ANY PORTIONS OF IT ARE FOUND DAMAGED, REPLACE EXISTING WATER DISTRIBUTION, REPLACE EXISTING PLUMBING FIXTURES, AND REPLACE EXISTING WATER HEATER. EXISTING WATER AND GAS METERS REMAIN.
5. MECHANICAL: REPLACE EXISTING HVAC WITH NEW HVAC SYSTEM, REPLACE EXISTING MECHANICAL DISTRIBUTION, AND REPLACE EXISTING EXHAUST FANS.
6. GENERAL: INSTALL A NEW FLAT ROOF ON HOME AND BACK PORCH, INSPECT ROOF OF FRONT PORCH AND GARAGE AND REPLACE AS MIGHT BE NECESSARY FROM THE RESULTS OF THE INSPECTION, REPAIR REAR FENCE ON WEST SIDE OF GARAGE AND REPAINT HOME EXTERIOR AS NECESSARY.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/11/2025 | RESIDENTIAL ADD/ALT v.1 | 09/02/2025 | APPROVED |
| 08/11/2025 | RESIDENTIAL ADD/ALT SIMPLE REVIEW v.1 | 08/11/2025 | REQUIRES RESUBMIT |
| 02/05/2026 | RESIDENTIAL ADD/ALT SIMPLE REVIEW REVISION v.1 | 02/20/2026 | APPROVED |
Conditions
Permit Number - TC-RES-0825-03916
Permit Status: Inspections
Permit Description: REV1: installation of 125 AMP Electrical Service in the subject
location, instead of the 200 AMP requested in the original set of Approved Construction Plans.
Additionally, instead of an overhead electrical line drop, there is an existing underground feeder line
which will be utilized (TEP is unable to provide an overhead line drop to the subject property)
THE SCOPE OF WORK INVOLVES THE REMEDIATION OF FIRE DAMAGE AND RENOVATION OF AN EXISTING TOWNHOME. MAJOR RENOVATIONS INCLUDE:
1. FINISHES: REPLACE ALL INTERIOR FINISHES, REPLACE DRYWALL AT CEILINGS AND INTERIOR WALLS, FUR OUT THE INTERIOR SIDE OF EXTERIOR NON-FRAMED WALLS (I.E. BLOCK WALLS) AND INSTALL NEW DRYWALL, REPLACE DOORS AND WINDOWS, AND REPLACE INSULATION.
2. STRUCTURAL: ADDRESS FINDINGS OF THE SOUTHWEST ENGINEERING, STRUCTURAL ENGINEERS, LLC STRUCTURAL INSPECTION REPORT SWE JOB# 2533 (SUBMITTED ALONG WITH THESE PLANS), INCLUDING DEMOLITION AND REBUILT OF FIRE DAMAGED BACK PORCH AND STORAGE, REPLACEMENT OF SIX SEVERELY FIRE DAMAGED ROOF RAFTERS AND TWO OTHER ROOF RAFTERS FOUND TO BE CRACKED, REINFORCEMENT OF TEN ROOF RAFTERS WITH MINOR FIRE DAMAGE, AND DEMOLITION AND REPLACEMENT OF APPROX. 546 SF OF FIRE DAMAGED ROOF SHEATHING OVER SAID RAFTERS. ADDITIONALLY, EXTEND FIRE WALLS BETWEEN SUBJECT AND ADJACENT TOWNHOMES TO A HEIGHT NOT LESS THAN 30" ABOVE ROOF BY INSTALLING FIREWALL PARAPETS, INSPECT AND REPAIR/REPLACE ANY OTHER DAMAGED ROOF RAFTERS AND OTHER ROOF FRAMING MEMBERS (IF ANY ARE FOUND TO BE DAMAGED), INSPECT AND REPLACE ANY DAMAGED ROOF DECKING, AND CREATE AN OPENING FROM THE KITCHEN TO THE LIVING ROOM.
3. ELECTRICAL: REPLACE EXISTING ELECTRICAL PANEL, ELECTRICAL DISTRIBUTION AND FIXTURES.
4. PLUMBING: INSPECT SEWER LINE FROM WITHIN THE HOME TO THE HCS AND REPAIR/REPLACE AS NECESSARY IF ANY PORTIONS OF IT ARE FOUND DAMAGED, REPLACE EXISTING WATER DISTRIBUTION, REPLACE EXISTING PLUMBING FIXTURES, AND REPLACE EXISTING WATER HEATER. EXISTING WATER AND GAS METERS REMAIN.
5. MECHANICAL: REPLACE EXISTING HVAC WITH NEW HVAC SYSTEM, REPLACE EXISTING MECHANICAL DISTRIBUTION, AND REPLACE EXISTING EXHAUST FANS.
6. GENERAL: INSTALL A NEW FLAT ROOF ON HOME AND BACK PORCH, INSPECT ROOF OF FRONT PORCH AND GARAGE AND REPLACE AS MIGHT BE NECESSARY FROM THE RESULTS OF THE INSPECTION, REPAIR REAR FENCE ON WEST SIDE OF GARAGE AND REPAINT HOME EXTERIOR AS NECESSARY.
| Date | Description | Comments |
|---|---|---|
| 08/11/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-RES-0825-03916
Permite Description: REV1: installation of 125 AMP Electrical Service in the subject
location, instead of the 200 AMP requested in the original set of Approved Construction Plans.
Additionally, instead of an overhead electrical line drop, there is an existing underground feeder line
which will be utilized (TEP is unable to provide an overhead line drop to the subject property)
THE SCOPE OF WORK INVOLVES THE REMEDIATION OF FIRE DAMAGE AND RENOVATION OF AN EXISTING TOWNHOME. MAJOR RENOVATIONS INCLUDE:
1. FINISHES: REPLACE ALL INTERIOR FINISHES, REPLACE DRYWALL AT CEILINGS AND INTERIOR WALLS, FUR OUT THE INTERIOR SIDE OF EXTERIOR NON-FRAMED WALLS (I.E. BLOCK WALLS) AND INSTALL NEW DRYWALL, REPLACE DOORS AND WINDOWS, AND REPLACE INSULATION.
2. STRUCTURAL: ADDRESS FINDINGS OF THE SOUTHWEST ENGINEERING, STRUCTURAL ENGINEERS, LLC STRUCTURAL INSPECTION REPORT SWE JOB# 2533 (SUBMITTED ALONG WITH THESE PLANS), INCLUDING DEMOLITION AND REBUILT OF FIRE DAMAGED BACK PORCH AND STORAGE, REPLACEMENT OF SIX SEVERELY FIRE DAMAGED ROOF RAFTERS AND TWO OTHER ROOF RAFTERS FOUND TO BE CRACKED, REINFORCEMENT OF TEN ROOF RAFTERS WITH MINOR FIRE DAMAGE, AND DEMOLITION AND REPLACEMENT OF APPROX. 546 SF OF FIRE DAMAGED ROOF SHEATHING OVER SAID RAFTERS. ADDITIONALLY, EXTEND FIRE WALLS BETWEEN SUBJECT AND ADJACENT TOWNHOMES TO A HEIGHT NOT LESS THAN 30" ABOVE ROOF BY INSTALLING FIREWALL PARAPETS, INSPECT AND REPAIR/REPLACE ANY OTHER DAMAGED ROOF RAFTERS AND OTHER ROOF FRAMING MEMBERS (IF ANY ARE FOUND TO BE DAMAGED), INSPECT AND REPLACE ANY DAMAGED ROOF DECKING, AND CREATE AN OPENING FROM THE KITCHEN TO THE LIVING ROOM.
3. ELECTRICAL: REPLACE EXISTING ELECTRICAL PANEL, ELECTRICAL DISTRIBUTION AND FIXTURES.
4. PLUMBING: INSPECT SEWER LINE FROM WITHIN THE HOME TO THE HCS AND REPAIR/REPLACE AS NECESSARY IF ANY PORTIONS OF IT ARE FOUND DAMAGED, REPLACE EXISTING WATER DISTRIBUTION, REPLACE EXISTING PLUMBING FIXTURES, AND REPLACE EXISTING WATER HEATER. EXISTING WATER AND GAS METERS REMAIN.
5. MECHANICAL: REPLACE EXISTING HVAC WITH NEW HVAC SYSTEM, REPLACE EXISTING MECHANICAL DISTRIBUTION, AND REPLACE EXISTING EXHAUST FANS.
6. GENERAL: INSTALL A NEW FLAT ROOF ON HOME AND BACK PORCH, INSPECT ROOF OF FRONT PORCH AND GARAGE AND REPLACE AS MIGHT BE NECESSARY FROM THE RESULTS OF THE INSPECTION, REPAIR REAR FENCE ON WEST SIDE OF GARAGE AND REPAINT HOME EXTERIOR AS NECESSARY.
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2025 | COT - RSBU - Roof Nailing | N/A | Partial Pass | still need bearing at porch rafters to house; can inspect this with intermediate. ok to install roofing. |
| 10/20/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | N/A | Partial Pass | 1. All The flex ductwork converging above the water heater is crushed and improperly installed, restricting airflow. Please reroute and install the ductwork correctly to ensure proper design airflow. 2. Water heater is not installed, can check at final at your own risk. Highly recommend installing at intermediate. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-RES-0825-03916
Permit Description: REV1: installation of 125 AMP Electrical Service in the subject
location, instead of the 200 AMP requested in the original set of Approved Construction Plans.
Additionally, instead of an overhead electrical line drop, there is an existing underground feeder line
which will be utilized (TEP is unable to provide an overhead line drop to the subject property)
THE SCOPE OF WORK INVOLVES THE REMEDIATION OF FIRE DAMAGE AND RENOVATION OF AN EXISTING TOWNHOME. MAJOR RENOVATIONS INCLUDE:
1. FINISHES: REPLACE ALL INTERIOR FINISHES, REPLACE DRYWALL AT CEILINGS AND INTERIOR WALLS, FUR OUT THE INTERIOR SIDE OF EXTERIOR NON-FRAMED WALLS (I.E. BLOCK WALLS) AND INSTALL NEW DRYWALL, REPLACE DOORS AND WINDOWS, AND REPLACE INSULATION.
2. STRUCTURAL: ADDRESS FINDINGS OF THE SOUTHWEST ENGINEERING, STRUCTURAL ENGINEERS, LLC STRUCTURAL INSPECTION REPORT SWE JOB# 2533 (SUBMITTED ALONG WITH THESE PLANS), INCLUDING DEMOLITION AND REBUILT OF FIRE DAMAGED BACK PORCH AND STORAGE, REPLACEMENT OF SIX SEVERELY FIRE DAMAGED ROOF RAFTERS AND TWO OTHER ROOF RAFTERS FOUND TO BE CRACKED, REINFORCEMENT OF TEN ROOF RAFTERS WITH MINOR FIRE DAMAGE, AND DEMOLITION AND REPLACEMENT OF APPROX. 546 SF OF FIRE DAMAGED ROOF SHEATHING OVER SAID RAFTERS. ADDITIONALLY, EXTEND FIRE WALLS BETWEEN SUBJECT AND ADJACENT TOWNHOMES TO A HEIGHT NOT LESS THAN 30" ABOVE ROOF BY INSTALLING FIREWALL PARAPETS, INSPECT AND REPAIR/REPLACE ANY OTHER DAMAGED ROOF RAFTERS AND OTHER ROOF FRAMING MEMBERS (IF ANY ARE FOUND TO BE DAMAGED), INSPECT AND REPLACE ANY DAMAGED ROOF DECKING, AND CREATE AN OPENING FROM THE KITCHEN TO THE LIVING ROOM.
3. ELECTRICAL: REPLACE EXISTING ELECTRICAL PANEL, ELECTRICAL DISTRIBUTION AND FIXTURES.
4. PLUMBING: INSPECT SEWER LINE FROM WITHIN THE HOME TO THE HCS AND REPAIR/REPLACE AS NECESSARY IF ANY PORTIONS OF IT ARE FOUND DAMAGED, REPLACE EXISTING WATER DISTRIBUTION, REPLACE EXISTING PLUMBING FIXTURES, AND REPLACE EXISTING WATER HEATER. EXISTING WATER AND GAS METERS REMAIN.
5. MECHANICAL: REPLACE EXISTING HVAC WITH NEW HVAC SYSTEM, REPLACE EXISTING MECHANICAL DISTRIBUTION, AND REPLACE EXISTING EXHAUST FANS.
6. GENERAL: INSTALL A NEW FLAT ROOF ON HOME AND BACK PORCH, INSPECT ROOF OF FRONT PORCH AND GARAGE AND REPLACE AS MIGHT BE NECESSARY FROM THE RESULTS OF THE INSPECTION, REPAIR REAR FENCE ON WEST SIDE OF GARAGE AND REPAINT HOME EXTERIOR AS NECESSARY.
Total Completed Inspections - 14
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2025 | COT - RSBU - Firewall/Fire Barrier/Firestop | Passed | ||
| 10/15/2025 | RSBU - Building Progress | Passed | ||
| 10/15/2025 | RSPL - Plumbing Progress | Passed | under ground plumbing approved. okay to backfill progress areas. shading material is required. 10/15/2025 | |
| 10/20/2025 | COT - RSPL - Gas Pressure Test | Passed | ||
| 10/20/2025 | COT - BULD - SWG Clearance | Passed | Southwest gas clearance: SWG | |
| 10/29/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 10.29.25 Corrections made, contractor is opting for wh at final. |
|
| 02/27/2026 | RSEL - Electrical Progress | Passed | ||
| 03/06/2026 | COT - RSEL - Electrical Underground | Passed | 3.6.26 Splice completed. This is a customer owned direct burial line that was pre existing. Originally a 200 amp panel was planned but revised with submission to a 125 amp service which was passed by RC. existing/grandfathered line is approved and notated. Proceed with incr to re-energize system. |
|
| 03/17/2026 | BULD - Electrical Clearance | Passed | INCR TEP |
|
| 06/17/2026 | COT - RSEL - Electrical Final | Passed | ||
| 06/17/2026 | COT - RSPL - Plumbing Final | Passed | ||
| 06/17/2026 | COT - RSME - Mechanical Final | Passed | ||
| 06/17/2026 | RSBU - Building Final | Passed | ||
| 06/17/2026 | COT - RSPL - Gas Final | Passed |